C
−
18
“b” Function
Run
Mode
Edit
Defaults
Func.
Code
Name
Description
Lnitial data Units
B120
Brake control enable
Two option codes:
00
…
Disable
01
…
Enable
U
00 -
b121
Brake Wait Time for Release
Set range: 0.00 to 5.00 sec
U
0.00 Sec
b122
Brake Wait Time for
Acceleration
Set range: 0.00 to 5.00 sec
U
0.00 Sec
b123
Brake Wait Time for
Stopping
Set range: 0.00 to 5.00 sec
U
0.00 Sec
b124
Brake Wait Time for
Confirmation
Set range: 0.00 to 5.00 sec
U
0.00 Sec
b125
Brake release freq.
Set range: 0 to 400Hz
U
0.00 Sec
b126
Brake release current
Set range: 0~200% of inverter
rated current
U
(rated
current)
A
b127
Braking freq. setting
Set range: 0 to 400Hz
U
0.00 Hz
B130
Deceleration overvoltage
suppression enable
00
…
Disabled
01
…
Enabled
02
…
Enabled with accel.
U
00
−
B131
Decel. overvolt. suppress
level
DC bus voltage of suppression.
Range is:
200V class
…
330 to 395
400V class
…
660 to 790
U
380
/760
V
b132
Decel. overvolt. suppress
const.
Accel. rate when b130=02.
Set range: 0.10 ~ 30.00 sec.
U
1.00 sec
B133
Decel. overvolt. suppress
proportional gain
Proportional gain when b130=01.
Range is: 0.00 to 5.00
9
0.20
−
B134
Decel. overvolt. suppress
integral time
Integration time when b130=01.
Range is: 0.00 to 150.0
9
1.0 sec
b145
GS input mode
Two option codes:
00
…
No trip (Hardware shutoff
only)
01
…
Trip
U
00 -
b150
Display ex.operator
connected
When an external operator is
connected via RS-422 port, the
built-in display is locked and shows
only one "d" parameter configured
in:
d001
~
d030
U
001
−
b160
1st parameter of Dual
Monitor
Set any two "d" parameters in b160
and b161, then they can be
monitored in d050. The two
parameters are switched by
up/down keys.
Set range:
d001
~
d030
U
001
−
b161
2nd parameter of Dual
Monitor
U
002
−
b163
Frequency set in monitoring
Two option codes:
00
…
Freq. set disabled
01
…
Freq. set enabled
9
00 -
Содержание WJ200 Series Software
Страница 19: ...xviii Revisions Revision History Table No Revision Comments Date of Issue Operation Manual No ...
Страница 59: ...2 14 Dimensional drawings continued Power Type W mm H mm D mm D1 mm 3 phase 200V WJ200 150LF 220 350 175 84 ...
Страница 295: ...4 92 Safe Stop Function To be finalized after TUV approval ...
Страница 296: ...5 1 5 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 ...
Страница 322: ...A 1 A Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 ...
Страница 378: ...B 49 Note 2 Be sure not to write into above 1F02h to 1F1Dh ...
Страница 382: ...C 1 Drive Parameter Setting Tables In This Appendix page Introduction 2 Parameter Settings for Keypad Entry 2 C ...