Add Frequency –
The inverter can add or subtract on offset value to the output
frequency setting which is specified by
A001
(will work with any of the five possible
sources). The ADD Frequency is a value you can store in parameter
A145
. the ADD
Frequency is summed with or subtracted from the output frequency setting only when
the [ADD] terminal is ON. Function
A146
selects whether to add or subtract. By
configuring an intelligent input as the [ADD] terminal, your application can selectively
apply the fixed value in
A145
to offset (positively or negatively) the inverter output
frequency in real time.
“A” Function
Run
Mode
Edit
Defaults
Func.
Code
Name
Description
Lnitial data
Units
A145
ADD frequency
An offset value that is applied
to the output frequency when
the [ADD] terminal is ON.
Range is 0.0 to 400.0 Hz
Two options:
00
…
Plus (adds
A145
value to
the output frequency
setting)
01
…
Minus (subtracts
A145
value from the output
frequency setting)
0.00 Hz
A146
ADD direction select
U
00
−
Keypad potentiometer
Control terminal
Function
F001
setting
ModBus network input
Calculate function output
Σ
+
A001
Frequency source setting
Output frequency setting
A145
ADD frequency
A146
ADD direction select
+/-
Intelligent input
[ADD]
Содержание WJ200 Series Software
Страница 19: ...xviii Revisions Revision History Table No Revision Comments Date of Issue Operation Manual No ...
Страница 59: ...2 14 Dimensional drawings continued Power Type W mm H mm D mm D1 mm 3 phase 200V WJ200 150LF 220 350 175 84 ...
Страница 295: ...4 92 Safe Stop Function To be finalized after TUV approval ...
Страница 296: ...5 1 5 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 ...
Страница 322: ...A 1 A Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 ...
Страница 378: ...B 49 Note 2 Be sure not to write into above 1F02h to 1F1Dh ...
Страница 382: ...C 1 Drive Parameter Setting Tables In This Appendix page Introduction 2 Parameter Settings for Keypad Entry 2 C ...