![Hitachi WJ200 Series Software Скачать руководство пользователя страница 226](http://html.mh-extra.com/html/hitachi/wj200-series-software/wj200-series-software_instruction-manual_140866226.webp)
4
−
23
Free-run Stop
When the terminal [FRS] is turned ON, the inverter stops the output and the motor
enters the free-run state (coasting). If terminal [FRS] is turned OFF, the output
resumes sending power to the motor if the Run command is still active. The free-run
stop feature works with other parameters to provide flexibility in stopping and starting
motor rotation.
In the figure below, parameter
B088
selects whether the inverter resumes operation
from 0 Hz (left graph) or the current motor rotation speed (right graph) when the [FRS]
terminal turns OFF. The application determines the best setting.
Parameter
B003
specifies a delay time before resuming operation from a free-run stop.
To disable this feature, use a zero delay time.
Option
Code
Terminal
Symbol
Function Name
State
Description
11
FRS
Free-run Stop
ON
Causes output to turn OFF, allowing motor to free
run (coast) to stop
OFF
Output operates normally, so controlled deceleration
and stops motor
Valid for inputs:
C001
~
C007
Example (requires input configuration—
see
page 3–84
):
See I/O specs on
page 4–6.
Required settings
B003
,
B088
,
C011
to
C017
Notes:
•
When you want the [FRS] terminal to be active
low (normally closed logic), change the setting
(
C011
to
C017
) that corresponds to the input
(
C001
to
C007
) that is assigned the [FRS]
function.
[FRS]
1
0
Motor speed
t
[FW,RV]
1
0
Zero frequency start
B088
=
00
[FRS]
1
0
Motor speed
t
[FW,RV]
1
0
Resume from motor speed
B088
=
01
B003
Wait time
FRS
7
6
5
4
3
2
1
L
PCS
P24
PLC
Содержание WJ200 Series Software
Страница 19: ...xviii Revisions Revision History Table No Revision Comments Date of Issue Operation Manual No ...
Страница 59: ...2 14 Dimensional drawings continued Power Type W mm H mm D mm D1 mm 3 phase 200V WJ200 150LF 220 350 175 84 ...
Страница 295: ...4 92 Safe Stop Function To be finalized after TUV approval ...
Страница 296: ...5 1 5 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 ...
Страница 322: ...A 1 A Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 ...
Страница 378: ...B 49 Note 2 Be sure not to write into above 1F02h to 1F1Dh ...
Страница 382: ...C 1 Drive Parameter Setting Tables In This Appendix page Introduction 2 Parameter Settings for Keypad Entry 2 C ...