C
−
17
“b” Function
Run
Mode
Edit
Defaults
Func.
Code
Name
Description
Lnitial data Units
B092
Cooling fan control
Selects when the fan is ON during
inverter operation, four options:
00
…
Fan is always ON
01
…
Fan is ON during run, OFF
during stop (5 minute delay
from ON to OFF)
02
…
Fan is temperature controlled
U
01 -
B093
Clear elapsed time of cooling
fan
Two option codes:
00
…
Count
01
…
Clear
U
00 -
b094
Initialization target data
Select initialized parameters, four
option codes:
00
…
All parameters
01
…
All parameters except
in/output terminals and
communication.
02
…
Only registered parameters in
U
xxx.
03
…
All parameters except
registered parameters in
U
xxx
and
b037
.
U
00 -
b095
Dynamic braking control
(BRD) selection
Three option codes:
00
…
Disable
01
…
Enable during run only
02
…
Enable always
U
01 -
b096
BRD activation level
Range is:
330 to 380V (200V class)
660 to 760V (400V class)
U
360/
720
V
B100
Free V/F setting, freq.1
Set range, 0 ~ value of
b102
U
0. Hz
b101
Free V/F setting, voltage.1
Set range, 0 ~ 800V
U
0.0 V
b102
Free V/F setting, freq.2
Set range, value of
b100
~
b104
U
0. Hz
b103
Free V/F setting, voltage.2
Set range, 0 ~ 800V
U
0.0 V
b104
Free V/F setting, freq.3
Set range, value of
b102
~
b106
U
0. Hz
b105
Free V/F setting, voltage.3
Set range, 0 ~ 800V
U
0.0 V
b106
Free V/F setting, freq.4
Set range, value of
b104
~
b108
U
0. Hz
b107
Free V/F setting, voltage.4
Set range, 0 ~ 800V
U
0.0 V
b108
Free V/F setting, freq.5
Set range, value of
b108
~
b110
U
0. Hz
b109
Free V/F setting, voltage.5
Set range, 0 ~ 800V
U
0.0 V
b110
Free V/F setting, freq.6
Set range, value of
b108
~
b112
U
0. Hz
b111
Free V/F setting, voltage.6
Set range, 0 ~ 800V
U
0.0 V
b112
Free V/F setting, freq.7
Set range,
b110
~ 400
U
0. Hz
b113
Free V/F setting, voltage.7
Set range, 0 ~ 800V
U
0.0 V
Содержание WJ200 Series Software
Страница 19: ...xviii Revisions Revision History Table No Revision Comments Date of Issue Operation Manual No ...
Страница 59: ...2 14 Dimensional drawings continued Power Type W mm H mm D mm D1 mm 3 phase 200V WJ200 150LF 220 350 175 84 ...
Страница 295: ...4 92 Safe Stop Function To be finalized after TUV approval ...
Страница 296: ...5 1 5 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 ...
Страница 322: ...A 1 A Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 ...
Страница 378: ...B 49 Note 2 Be sure not to write into above 1F02h to 1F1Dh ...
Страница 382: ...C 1 Drive Parameter Setting Tables In This Appendix page Introduction 2 Parameter Settings for Keypad Entry 2 C ...