CAUTION: EFFECTS OF POWER DISTRIBUTION SYSTEM ON INVERTER
In the case below involving a general-purpose inverter, a large peak current can flow on the
power supply side, sometimes destroying the converter module:
1.
The unbalance factor of the power supply is 3% or higher.
2.
the power supply capacity is at least 10 times greater than the inverter capacity (or the
power supply capacity is 500kVA or more).
3.
Abrupt power supply changes are expected, due to conditions such as:
a. Several inverters are interconnected with a short bus.
b. A thyristor converter and an inverter are interconnected with a short bus.
c. An installed phase advance capacitor opens and closes.
Where these conditions exist or when the connected equipment must be highly reliable, you
MUST install an input side AC-reactor of 3% (at a voltage drop at rated current) with respect to
the supply voltage on the power supply side. Also, where the effects of an indirect lightening
strike are possible, install a lightening conductor.
CAUTION: SUPPRESSION FOR NOISE INTERFERENCE FROM INVERTER
The inverter uses many semiconductor switching elements such as transistors and IGBTs. Thus,
a radio receiver or measuring instrument located near the inverter is susceptible to noise
interference.
To protect the instruments from erroneous operation due to noise interference, they should be
used well away from the inverter. It is also effective to shield the whole inverter structure.
The addition of an EMI filter on the input side of the inverter also reduces the effect of noise
from the commercial power line on external devices.
Note that the external dispersion of noise from the power line can be minimized by connecting
an EMI filter on the primary side of the inverter.
•
SFEF model has integrated filter complies to EN61800-3 category C1.
•
HFEF model has integrated filter complies to EN61800-3 category C2.
EMI Filter
CAUTION: When the EEPROM error E08 occurs, be sure to confirm the setting values again.
CAUTION: When using normally closed active state settings (C011 to C017) for externally
commanded Forward or Reverse terminals [FW] or [RV], the inverter may start automatically
when the external system is powered OFF or disconnected from the inverter! So do not use
normally closed active state settings for Forward or Reverse terminals [FW] or [RV] unless your
system design protects against unintended motor operation.
R1
S1
T1
R2
S2
T2
Inverter
L1
L2
L3
U
V
W
Motor
EMI Filter
Inverter
Motor
Remote
Operator
Completely ground the
enclosure panel, metal
screen, etc. with as short
a wire as possible.
noise
Grounded frame
Conduit or shielded cable
-- to be grounded
Содержание WJ200 Series Software
Страница 19: ...xviii Revisions Revision History Table No Revision Comments Date of Issue Operation Manual No ...
Страница 59: ...2 14 Dimensional drawings continued Power Type W mm H mm D mm D1 mm 3 phase 200V WJ200 150LF 220 350 175 84 ...
Страница 295: ...4 92 Safe Stop Function To be finalized after TUV approval ...
Страница 296: ...5 1 5 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 ...
Страница 322: ...A 1 A Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 ...
Страница 378: ...B 49 Note 2 Be sure not to write into above 1F02h to 1F1Dh ...
Страница 382: ...C 1 Drive Parameter Setting Tables In This Appendix page Introduction 2 Parameter Settings for Keypad Entry 2 C ...