4. Set the Motor Current –
The inverter has thermal overload protection that is
designed to protect the inverter and motor from overheating due to an excessive load.
The inverter’s uses the motor’s current rating to calculate the time-based heating effect.
This protection depends on using correct current rating for your motor. The level of
electronic thermal setting, parameter
B012
, is adjustable from 20% to 100% of the
inverter’s rated current. A proper configuration will also help prevent unnecessary
inverter trip events.
Read the motor’s current rating on its manufacturer’s nameplate. Then follow the steps
below to configure the inverter’s overload protection setting.
Action
Display
Func./Parameter
(Starting point)
A082
AVR voltage select
Press the ESC key.
b001
First “B” Group parameter selected
Press the
U
key and hold until
Æ
b012
Level of electronic thermal setting
Press the SET key.
b160
Default value will be 100% of inverter
rated current
Press the
U
/
V
key to select
b140
Set to your motor specs (your display
may be different)
Press the SET key.
b012
Store parameter, returns to “
b012
”
Содержание WJ200 Series Software
Страница 19: ...xviii Revisions Revision History Table No Revision Comments Date of Issue Operation Manual No ...
Страница 59: ...2 14 Dimensional drawings continued Power Type W mm H mm D mm D1 mm 3 phase 200V WJ200 150LF 220 350 175 84 ...
Страница 295: ...4 92 Safe Stop Function To be finalized after TUV approval ...
Страница 296: ...5 1 5 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 ...
Страница 322: ...A 1 A Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 ...
Страница 378: ...B 49 Note 2 Be sure not to write into above 1F02h to 1F1Dh ...
Страница 382: ...C 1 Drive Parameter Setting Tables In This Appendix page Introduction 2 Parameter Settings for Keypad Entry 2 C ...