3
−
116
Simple positioning setting
- Set
“
03
” in [EA] selection (
P003
), then pulse train input is used as feedback signal from encoder.
- Set
"
02
" in simple positioning selection (
P012
), then simple positioning is enabled. (If "
00
" is set, "V/f
control with FB" is enabled. Please refer to xx for further information.
- Up to 8 position data are commanded by combination of 3 input terminals configured as CP1 to
CP3.
- Besides positioning input, RUN command (FW,RV) is necessary. Since rotation direction does not
matter for positioning, both FW and RV work as RUN command.
- Positioning speed depends on frequency source (
A001
).
- More than four digits are required for positioning data, but only four higher digits are displayed.
Code
Item
Data or data range
Description
P003
[EA] terminal selection
01
Encoder feedback
P004
Feedback pulse train mode
00
Single phase pulse train
01
90
°
ph. difference 2-ph. pulse train 1
02
90
°
ph. difference 2-ph. pulse train 2
03
Single phase pulse train + direction
P011
Encoder PPR setting
32. to 1024.
P012
Simple positioning selection
02
Simple positioning enabled
P015
Creep speed
Start freq. to .10.00Hz
P026
Over-speed error detection level
0.0 to 150. %
P027
Speed deviation error level
0.00 to 120.0 Hz
p072
Position range (Forward)
0 to +268435455
Higher 4-digits displayed
p073
Position range (Reverse)
–268435455 to 0
Higher 4-digits displayed
p075
Positioning mode selection
00
With limitation
01
No limitation (shorter route)
p004
is to be set
00
or
01
P077
Encoder disconnection timeout
0.0 to 10.0 s
H050
Slip comp. P gain for FB V/f
0.0 to 10.00
H051
Slip comp. I gain for FB V/f
0.0 to 1000. s
d029
Position setting monitor
8435455 to +268435455
d030
Position feedback monitor
C102
Reset selection
03
Internal data is not cleared by reset
C001
-C007
Input [1]~[7] function
47
PCLR: Pulse counter clear
85
EB: Rotation direction detection
C021-C022
C026
Output [11][12] function
Alarm relay function
22
DSE: Speed deviation excessive
23
POK: Positioning competion
(Note 1) If 7/EB terminal is used (P004=00~03), set 85 (EB) in input 7 (C007). ON is forward
and OFF is reverse direction.
Содержание WJ200 Series Software
Страница 19: ...xviii Revisions Revision History Table No Revision Comments Date of Issue Operation Manual No ...
Страница 59: ...2 14 Dimensional drawings continued Power Type W mm H mm D mm D1 mm 3 phase 200V WJ200 150LF 220 350 175 84 ...
Страница 295: ...4 92 Safe Stop Function To be finalized after TUV approval ...
Страница 296: ...5 1 5 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 ...
Страница 322: ...A 1 A Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 ...
Страница 378: ...B 49 Note 2 Be sure not to write into above 1F02h to 1F1Dh ...
Страница 382: ...C 1 Drive Parameter Setting Tables In This Appendix page Introduction 2 Parameter Settings for Keypad Entry 2 C ...