![Hitachi WJ200 Series Software Скачать руководство пользователя страница 114](http://html.mh-extra.com/html/hitachi/wj200-series-software/wj200-series-software_instruction-manual_140866114.webp)
3
−
33
PID Loop Configuration
The inverter’s PID loop algorithm is configurable for various applications.
PID Output Limit -
The PID loop controller has a built-in output limit function. This
function monitors the difference between the PID setpoint and the loop output (inverter
output frequency), measured as a percentage of the full scale range of each. The limit is
specified by parameter
A078
.
•
When the difference |(Setpoint – loop output)| is smaller than or equal to the
A078
limit value, the loop controller operates in its normal linear range.
•
When the difference |(Setpoint – loop output)| is larger than the
A078
limit value,
the loop controller changes the output frequency as needed so that the difference
does not exceed the limit.
The diagram below shows PID setpoint changes and the related output frequency
behavior when a limit value in
A078
exists.
Deviation (error) Inversion -
In typical heating loops or ventilation loops, an increase in
energy into the process results in an
increasing
PV. In this case, the Loop Error = (SP –
PV). For cooling loops, an increase in energy into the process results in a
decreasing
PV.
In this case, the Loop Error = –(SP – PV). Use
A077
to configure the error term.
t
Output limit
PID Setpoint
Output limit
Limit imposed
on output
Limit imposed
on output
A078
A078
%
Output freq.
Σ
PID
calculation
SP
+
Error
Freq.
PV
-
PV from process with
positive correlation
A077
=
00
Σ
PID
calculation
SP
-
Error
Freq.
PV
+
PV from process with
negative correlation
A077
=
01
Содержание WJ200 Series Software
Страница 19: ...xviii Revisions Revision History Table No Revision Comments Date of Issue Operation Manual No ...
Страница 59: ...2 14 Dimensional drawings continued Power Type W mm H mm D mm D1 mm 3 phase 200V WJ200 150LF 220 350 175 84 ...
Страница 295: ...4 92 Safe Stop Function To be finalized after TUV approval ...
Страница 296: ...5 1 5 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 ...
Страница 322: ...A 1 A Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 ...
Страница 378: ...B 49 Note 2 Be sure not to write into above 1F02h to 1F1Dh ...
Страница 382: ...C 1 Drive Parameter Setting Tables In This Appendix page Introduction 2 Parameter Settings for Keypad Entry 2 C ...