Order No. 2104 ..
Object for setpoint temperature specification
Function:
Setpoint temperature specification
Object
h
50
Function
Setpoint temperature
Name
C.Input
Type
2
bytes
DPT
9,001
Flag
C, -, T, R
Description
2-byte object for external setting of the temperature setpoint. Depending on
the operating mode, the possible range of values is limited by the configured
frost protection and/or heat protection temperature.
The temperature value must always be specified in the format "°C".
Object for basic setpoint shift (only for relative setpoint presetting)
Function:
Basic setpoint shifting
Object
h
52
Function
Current setpoint shifting
Name
C.Output
Type
1
bytes
DPT
6,010
Flag
C, -, T, R
Description
1-byte object for giving feedback on the current setpoint shifting. The value of
a counter value in the communication object corresponds to the configured
interval of the basic setpoint shift. The value "0" means that no shift is active .
The value is depicted in a double complement in the positive and negative
direction.
This object is only available in this way if relative setpoint presetting is
configured.
Function:
Basic setpoint shifting
Object
h
53
Function
Preset setpoint shifting
Name
C.Input
Type
1
bytes
DPT
6,010
Flag
C, W, -,
(R)
1
Description
1-byte object for presetting a basic setpoint shift. The value of a counter value
in the communication object corresponds to the configured interval of the
basic setpoint shift. The value "0" means that no shift is active . The value is
depicted in a double complement in the positive and negative direction.
In case the limits of the value range are exceeded by the preset external
value, the controller will automatically reset the received value to the minimum
and maximum limits.
This object is only available in this way if relative setpoint presetting is
configured.
1: Each communication object can be read out. For reading, the R-flag must be set.
Page 34 of 171
Software "KNX CO2 sensor"
Object table
Содержание CO2-Sensor
Страница 42: ...Order No 2104 Figure 7 CO2 concentration Page 42 of 171 Software KNX CO2 sensor Functional description...
Страница 74: ...Order No 2104 Page 74 of 171 Software KNX CO2 sensor Functional description...
Страница 165: ...Order No 2104 See channel 1 Disable Page 165 of 171 Software KNX CO2 sensor Parameters...