Order No. 2104 ..
The parameter is only visible in the
"Heating" or "Heating and cooling"
operating mode (if necessary with
additional levels) and only with relative
setpoint presetting.
Change-over between
heating and cooling
automatic
via object (heating/cooling
change-over)
In a configured mixed mode it is
possible to switch over between heating
and cooling.
With "Automatic": Depending on the
operating mode and the room
temperature, the change-over takes
place automatically.
With "via object (heating/cooling
change-over)": The change-over takes
place only via the object
"Heating/cooling change-over".
With automatic setpoint presetting this
parameter is permanently set to "Via
object (heating/cooling change-over)"!
Heating / cooling mode
after a reset
Heating
Cooling
Operating mode before
reset
The preset operating mode for after the
return of the bus voltage is specified
here.
Only visible if "Change-over between
heating and cooling = via object"!
Automatic
heating/cooling
transmission switchover
on changing the
operating mode
on changing the output
value
Here, it is possible to specify when a
telegram is transmitted automatically
onto the bus via the object "Heating /
cooling change-over".
Only visible if "Change-over between
heating and cooling = automatic".
Cyclical transmission
heating/cooling change-
over
(0...255) * 1 min;
0 = inactive
0
...255
This parameter specifies whether the
current object status of the "Heating /
cooling change-over" object should be
output cyclically to the bus on an
automatic change-over. The cycle time
can be set here. The "0" setting
deactivates the periodic transmission of
the object value.
Only visible if "Change-over between
heating and cooling = automatic".
h
Room temperature control -> Controller functionality
Presence detection
none
Presence button
Presence detector
In the "None" setting, the presence
mode is deactivated.
In the "Presence button" setting,
presence detection takes place via the
presence object (e.g. other push-button
sensors). When the presence button is
pressed from the night mode or
frost/heat protection, the comfort
Page 140 of 171
Software "KNX CO2 sensor"
Parameters
Содержание CO2-Sensor
Страница 42: ...Order No 2104 Figure 7 CO2 concentration Page 42 of 171 Software KNX CO2 sensor Functional description...
Страница 74: ...Order No 2104 Page 74 of 171 Software KNX CO2 sensor Functional description...
Страница 165: ...Order No 2104 See channel 1 Disable Page 165 of 171 Software KNX CO2 sensor Parameters...