Order No. 2104 ..
4.2.4.4.3 Adapting the control algorithms
Adapting the PI control
There are several systems available, which may heat or cool a room. One option is to uniformly
heat or cool the surroundings via heat transfer media (preferably water or oil) in connection with
room air convection. Such systems are used, for example, with wall mounted heaters,
underfloor heating or cooling ceilings.
Alternatively or additionally forced air systems may heat or cool rooms. In most cases such
systems are electrical forced hot air systems, forced cool air systems or refrigerating
compressors with fan. Due to the direct heating of the room air such heating and cooling
systems work quite swiftly.
The control parameters need to be adjusted so that the PI control algorithm may efficiently
control all common heating and cooling systems thus making the room temperature control
work as fast as possible and without deviation. Certain factors can be adjusted with a PI control
that can influence the control behaviour quite significantly at times. For this reason, the room
temperature controller can be set to predefined ‘experience values’ for the most common
heating and cooling systems. In case the selection of a corresponding heating or cooling system
does not yield a satisfactory result with the default values, the adaptation can optionally be
optimised using control parameters.
Predefined control parameters for the heating or cooling stage and, if applicable, also for the
additional stages are adjusted via the "type of heating" or "type of cooling" parameters. These
fixed values correspond to the practical values of a properly planned and executed air
conditioning system and will result in an ideal behaviour of the temperature control. The heating
and cooling types shown in the following tables can be specified for heating and cooling
operation.
Type of heating
Proportional
range (preset)
Reset time
(preset)
Recommended
PI control type
Recommended
PWM cycle time
Heat water
heating
5 Kelvin
150
minutes
Continuous / PWM 15 min.
Underfloor heating
5 Kelvin
240
minutes
PWM
15-20 min.
Electrical heating
4 Kelvin
100
minutes
PWM
10-15 min.
Fan coil unit
4 Kelvin
90 minutes
Continuous
---
Split unit (split
climate control unit)
4 Kelvin
90 minutes
PWM
10-15 min.
Table 2: Predefined control parameters and recommend control types for heating systems
Cooling type
Proportional
range (preset)
Reset time
(preset)
Recommended
PI control type
Recommended
PWM cycle time
Cooling ceiling
5 Kelvin
240
minutes
PWM
15-20 min.
Fan coil unit
4 Kelvin
90 minutes
Continuous
---
Split unit (split
climate control unit)
4 Kelvin
90 minutes
PWM
10-15 min.
Table 3: Predefined control parameters and recommend control types for cooling systems
Page 75 of 171
Software "KNX CO2 sensor"