Order No. 2104 ..
Automatic transmission
at modification by
(0...100) * 1 %;
0 = inactive
0...
3
...100
This parameter determines the size of
the command value change that will
automatically transmit continuous
command value telegrams via the
command value objects. Thus this
parameter only affects command values
which are configured to "Continuous PI
control" and to the 1 byte additional
command value objects of the
"Switching PI control (PWM)".
Cycle time of the
switching command
value
(1...255) * 1 min
1...
15
...255
This parameter specifies the cycle time
for the pulse width modulated command
value (PWM). Thus this parameter only
affects command values which are
configured to "Switching PI control
(PWM)".
Cycle time for automatic
transmission
(0...255) * 1 min;
0 = inactive
0...
10
...255
This parameter determines the time
interval for the cyclical transmission of
the command values via all command
value objects.
Output of the heating
variable
Inverted (under current, this
means closed)
Normal (under current,
this means opened)
At this point, it is possible to specify
whether the command value telegram
for heating is output normally or in
inverted form.
This parameter is only visible if the
operating mode "Heating" or "Heating
and cooling" is configured and not two-
level operation.
Output of the command
value basic level
heating
Inverted (under current, this
means closed)
Normal (under current,
this means opened)
At this point, it is possible to specify
whether the command value telegram
for the heating basic level is output
normally or in inverted form.
This parameter is only visible if the
operating mode "Heating" or "Heating
and cooling" is configured along with
two-level operation.
Output of the heating
additional stage variable
Inverted (under current, this
means closed)
Normal (under current,
this means opened)
At this point, it is possible to specify
whether the command value telegram
for the heating additional level is output
normally or in inverted form.
This parameter is only visible if the
operating mode "Heating" or "Heating
and cooling" is configured along with
two-level operation.
Output of the cooling
variable
Inverted (under current, this
means closed)
At this point, it is possible to specify
whether the command value telegram
for cooling is output normally or in
Page 129 of 171
Software "KNX CO2 sensor"
Parameters