Order No. 2104 ..
Function:
Status signal
Object
h
36
Function
KNX status operating mode
Name
C.Output
Type
1
bytes
DPT
20,102
Flag
C, -, T, (R)
1
Description
1-byte object used by the controller to output the current operating mode. This
object is generally used to enable controller extensions to display the
controller operating mode correctly in the KNX compliant status display.
Therefore this object should be connected with controller extensions if the
KNX compliant status feedback is not configured.
Only when "Controller status" = "KNX compliant".
Function:
Status signal
Object
h
55
Function
KNX status
Name
C.Output
Type
2
bytes
DPT
22,101
Flag
C, -, T, (R)
1
Description
2-byte object that the controller uses to display elementary basic functions in a
KNX-harmonised manner.
Only when "Controller status" = "KNX compliant".
Function:
Status signal
Object
h
56
Function
KNX status forced oper.
mode
Name
C.Output
Type
1
bytes
DPT
20,102
Flag
C, -, T, (R)
1
Description
1-byte object used by the controller to output the operating mode in the event
of forced position. This object is generally used to enable controller extensions
to display the controller operating mode correctly in the KNX compliant status
display. Therefore this object should be connected with controller extensions if
the KNX compliant status feedback is not configured.
Only when "Controller status" = "KNX compliant".
Objects for command value limit
Function:
Command value limit
Object
h
57
Function
Command value limit
Name
C.Input
Type
1-bit
DPT
1,001
Flag
C, W, -, (R)
1
Description
1-bit object for activating or deactivating the command value limit.
Polarity: Limitation activated ="1", Limitation deactivated = "0".
1: Each communication object can be read out. For reading, the R-flag must be set.
Page 26 of 171
Software "KNX CO2 sensor"
Object table
Содержание CO2-Sensor
Страница 42: ...Order No 2104 Figure 7 CO2 concentration Page 42 of 171 Software KNX CO2 sensor Functional description...
Страница 74: ...Order No 2104 Page 74 of 171 Software KNX CO2 sensor Functional description...
Страница 165: ...Order No 2104 See channel 1 Disable Page 165 of 171 Software KNX CO2 sensor Parameters...