Order No. 2104 ..
(4 K / 90 min)
Split unit (4 K / 90 min)
via control parameter
With the "Using control parameters"
setting, it is possible to set the control
parameters in a manner deviating from
the predefined values within specific
limits.
This parameter is only visible if "Type of
cooling control = PI control".
Proportional range
cooling
(10 ... 127) * 0.1 K
10...
50
...127
Separate setting of the "Proportional
range" control parameter.
This parameter is only visible if "Type of
cooling = via control parameter" and the
cooling control type "PI control".
Reset time cooling
(0 ... 255) * 1 min;
0 = inactive
0...
240
...255
Separate setting of the "Reset time"
control parameter.
This parameter is only visible if "Type of
cooling = via control parameter" and the
cooling control type "PI control".
Top hysteresis of the
2-point controlling
cooling
(5 ... 127) * 0.1 K
5
...127
Definition of top hysteresis (switch-on
temperatures) of the cooling.
This parameter is only visible if "Type of
cooling control = Switching 2-point
feedback control (ON/OFF)".
Bottom hysteresis of the
2-point controlling
cooling
(-128 ... –5) * 0.1 K
-128...
-5
Definition of bottom hysteresis (switch-
off temperatures) of the cooling.
This parameter is only visible if "Type of
cooling control = Switching 2-point
feedback control (ON/OFF)".
Operating mode switch-
over
via value (1 byte)
via switching (4 x 1 bit)
In the setting "via value (1-byte) the
change-over of the operating modes via
the bus takes place according to the
KNX specification via a 1-byte value
object. In addition, a higher-ranking
forced object is available for this setting.
In the setting "via switching (4 x 1 bit)"
the ‘classic’ change-over of the
operating modes via the bus is via four
separate 1-bit objects.
Operation mode after
reset
Restore operating mode
before reset
Comfort mode
Standby mode
Night operation
Frost/heat protection mode
This parameter specifies which
operating mode is set immediately after
a device reset.
With "Restore operation mode before
reset": The mode set before a reset
according to the operating mode object
will be restored after the initializing
phase of the device. Operating modes
set by a function with a higher priority
before the reset (Forced, Window
Page 127 of 171
Software "KNX CO2 sensor"
Parameters