Order No. 2104 ..
Time between short and
long time operation,
Base
130 ms
260 ms
520 ms
1 sec
2.1 sec
4.2 sec
8.4 sec
17 sec
34 sec
Time after which the function of a long
actuation is executed. Only for operation
concept = "short – long – short".
Time = Basic x Factor
Time between short and
long time operation,
Factor (4...127)
4
...127
Time after which the function of a long
actuation is executed. Only for operation
concept = "short – long – short".
Time = Basic x Factor
Presetting: 130 ms × 4 = 520 ms
Slat adjusting time,
Base
130 ms
260 ms
520 ms
1 sec
2.1 sec
4.2 sec
8.4 sec
17 sec
34 sec
Time during which a MOVE telegram for
slat adjustment can be terminated by
releasing the push-button at the input.
Time = Basic x Factor
Slat adjusting time,
Factor (3...127)
3...
20
...127
Time during which a MOVE telegram for
slat adjustment can be terminated by
releasing the push-button at the input.
Time = Basic x Factor
Presetting: 130 ms × 20 = 2.6 s
Behaviour after bus
voltage
return
no reaction
UP
DOWN
It is possible to specify which reaction
should take place after bus voltage
return. The configured delay time after
reset or bus voltage return must first
have elapsed before the pre-set reaction
is executed here.
With "no reaction", no reaction occurs.
With "UP" a MOVE telegram (up) is
transmitted.
With "DOWN" a MOVE telegram (down)
is transmitted.
Function channel 1 =
"Value transmitter"
Page 148 of 171
Software "KNX CO2 sensor"
Parameters