Order No. 2104 ..
(0...255) * 1 min;
0 = inactive
controller. In this case the
communication partner (e.g. controller
extension) must transmit its temperature
value itself.
This parameter is only visible when the
temperature detection system requires
that a temperature value is received.
Transmission when
room temperature
change by
(0...255) * 0.1 K; 0 =
inactive
0...
3
...255
Determines the size of the value change
of the room temperature after which the
current values are automatically
transmitted on the bus via the "Actual
temperature" object.
Cyclical transmission of
room temperature
(0...255) * 1 min;
0 = inactive
0...
15
...255
This parameter specifies whether and
when the determined room temperature
is to be periodically output via the
"Actual temperature" object.
h
Sensor -> humidity measurement
Transmit on change of
the measured value by
(Transmission delay:
10 s)
inactive
0.5%
1%
3%
10%
So as not to burden the bus with very
frequent telegrams, the measured value
should not be sent for every tiny change.
While taking the measurement task into
account, a maximum possible value
should be set here.
The setting here refers to the measuring
range of the humidity measurement
(here: 100% RH).
Cycl. sending of the
measured value
(0...120) * 10 s;
0 = inactive
0
...120
Here you can set whether and within
which time interval the value is
transmitted. The set value multiplied by
10 is the repeat time in seconds. It is
thus possible to set the cycle time in
step widths of 10 seconds.
The value "0" means that no cyclic
sending is carried out.
Limiting values
Inactive
1 Limiting value active
2 Limiting values active
Here you can set whether and how
many limiting values are activated for
the humidity measurement.
Behaviour of the limiting
values in frost/heat
protection mode of the
controller,
Operating mode heating
and
operating mode cooling
No action
send ON
send OFF
ON, no telegram
OFF, no telegram
If the controller changes to the operating
mode frost/heat protection, then the
behaviour of the limiting values
parameterised here is executed in
frost/heat protection mode according to
the operating mode of the controller.
In the "no action" setting, the behaviour
of all limiting values of the measured
Page 120 of 171
Software "KNX CO2 sensor"
Parameters