Order No. 2104 ..
It is possible to configure "Heating", "Cooling" or alternatively the mixed mode "Heating and
Cooling" as the operating mode. Using the additional stages is also possible. In this connection,
you can set different control algorithms for the heating and/or cooling system. Thus, you can
use up to four separate algorithms for two-stage heating or cooling operation.
The command values calculated by the control algorithm are output via the "Heating command
value" or "Cooling command value" communication objects. Depending on the control algorithm
selected for the heating and/or cooling mode, the format of the command value objects is,
among other things, also specified. 1-bit or 1-byte actuating objects can be created in this way
Regler Regelstrecke (T-id=964872587 L-id=1014951692 Link auf Ressource). The control
algorithm is specified by the parameters "Type of heating control" or "Type of cooling control" in
the "Room temperature control -> Controller general" parameter branch and, if necessary, also
with a distinction of the basic and additional stages.
Continuous PI control
PI control is an algorithm which consists of a proportional part and an integral part. Through the
combination of these control properties, you can obtain room temperature control as quickly and
precisely as possible without or only with low deviations.
When you use this algorithm, the room temperature controller will calculate a new continuous
command value in cycles of 30 seconds and send it to the bus via a 1-byte value object if the
calculated command value has changed by a specified percentage. You can use the "Automatic
transmission on change by…" parameter in the "Room temperature control -> Command value
and status output" parameter branch to set the change interval in percent.
Figure 18: Continuous PI control
An additional heating or cooling level as PI control works in the same way as the PI control of
the basic level, with the exception that the setpoint will shift, taking account of the configured
level width.
Switching PI control
With this type of feedback control, the room temperature will also be kept constant by the PI
control algorithm. Taking the mean value for a given time, the same behaviour of the control
system will result as you would obtain with a continuous controller. The difference compared
with continuous feedback control is only the way how the command value is output. The
command value calculated by the algorithm in cycles of every 30 seconds is internally
converted into a pulse-width-modulated (PWM) command value signal and sent to the bus via a
1-bit switching object after the cycle time has elapsed. The mean value of the command value
signal resulting from this modulation, taking into account the adjustable cycle time (parameter
Page 68 of 171
Software "KNX CO2 sensor"
Functional description
Содержание CO2-Sensor
Страница 42: ...Order No 2104 Figure 7 CO2 concentration Page 42 of 171 Software KNX CO2 sensor Functional description...
Страница 74: ...Order No 2104 Page 74 of 171 Software KNX CO2 sensor Functional description...
Страница 165: ...Order No 2104 See channel 1 Disable Page 165 of 171 Software KNX CO2 sensor Parameters...