Order No. 2104 ..
For this heating/cooling operating mode, the setpoint temperatures of both heating/cooling
modes exist for the Comfort, Standby and Night operating modes as well as the deadband. A
distinction is made in the deadband position with combined heating and cooling. A symmetrical
or an asymmetrical deadband position can be configured. In addition, the frost protection and
the heat protection temperatures can be preset.
The following applies…
T
Standby setpoint heating
≤ T
Comfort setpoint heating
≤ T
Comfort setpoint cooling
≤ T
Standby setpoint cooling
or
T
Night setpoint heating
≤ T
Comfort setpoint heating
≤ T
Comfort setpoint cooling
≤ T
Night setpoint cooling
The set-temperatures for "Standby" and "Night" are derived from the comfort setpoint
temperatures for heating or cooling. The temperature increase (for cooling) and the temperature
decrease (for heating) of both operating modes can be preset in ETS. The comfort temperatures
itself are derived from the deadband and the basic setpoint.
The frost protection is supposed to prevent the heating system from freezing. For this reason
the frost protection temperature (default: +7 °C) should be set to a smaller value than the night
temperature for heating. In principle, however, it is possible to select frost protection
temperature values b7.0 °C and +40.0 °C. The heat protection is supposed to ensure
that the temperature does not exceed the maximum permissible room temperature in order to
protect system components. For this reason the heat protection temperature (default: +35 °C)
should be set to a larger value than the night temperature for cooling. In principle, however, it is
possible to select heat protection temperature values b7.0 °C and +45.0 °C.
The possible range of values for a setpoint temperature ("heating and cooling") lies between
+7.0 °C and +45.0 °C and is bounded by the frost protection temperature in the lower range and
by the heat protection temperature in the upper range.
The level offset configured in ETS will be additionally considered in a two-level heating or
cooling mode.
Page 92 of 171
Software "KNX CO2 sensor"
Functional description