Order No. 2104 ..
Function:
Operating mode switchover
Object
h
35
Function
Heating / cooling switchover
1
Name
C.Output
Type
1-bit
DPT
1,100
Flag
C, -, T, (R)
2
Description
1 bit object to transmit the automatically set operating mode of the controller.
Object value "1" = Heating; Object value "0" = Cooling.
Object for controller status
Function:
Status signal
Object
h
36
Function
Controller status
Name
C.Output
Type
1
bytes
DPT
---
3
Flag
C, -, T, (R)
2
Description
1-byte object used by the controller to output the current state of operation
(e.g. to a controller extension).
Only when "Controller status" = "Controller general".
Function:
Status signal
Object
h
54
Function
Status signal addition
Name
C.Output
Type
1
bytes
DPT
---
4
Flag
C, -, T, (R)
2
Description
1-byte object used by the controller to output the current enlarged state of
operation (e.g. to a controller extension).
Only when "Controller status" = "Controller general".
Function:
Status signal
Object
h
36
Function
Controller status ...
Name
C.Output
Type
1-bit
DPT
1,001
Flag
C, -, T, (R)
2
Description
1-bit object for single status feedback of configured controller functions. This
object is only available in this way when a part of the controller status is to be
transmitted singly as 1-bit information (parameter-dependent).
1: This object is only active with one control circuit in the "heating and cooling" or "basic
/additional - heating/ cooling" mixed-mode operation.
2: Each communication object can be read out. For reading, the R-flag must be set.
3: Non-standardised DP type (in accordance with KNX AN 097/07 rev 3).
4: Non-standardised DP type.
Page 25 of 171
Software "KNX CO2 sensor"
Object table