Order No. 2104 ..
4.2.5 Parameters
4.2.5.1 Parameter sensor
Description
Values
Comment
h
Sensor
h
Sensor -> CO2 measurement
Height of location above
sea level
(0...2000) * 1 m
0...
500
...2000
The measured value of the CO
2
sensor
module is air pressure dependent. The
parameter "Height of location above sea
level" is provided in order to
compensate for this dependency. The
user can enter the current location
height freely here.
Transmit on change of
the measured value by
(Transmission delay:
10 s)
inactive
0.5%
1%
3%
10%
So as not to burden the bus with very
frequent telegrams, the measured value
should not be sent for every tiny change.
While taking the measurement task into
account, a maximum possible value
should be set here.
The setting here refers to the measuring
range of the CO
2
measurement
(here: 2000 ppm).
Cycl. sending of the
measured value
(0...120) * 10 s;
0 = inactive
0
... 120
Here you can set whether and within
which time interval the value is
transmitted. The set value multiplied by
10 is the repeat time in seconds. It is
thus possible to set the cycle time in
step widths of 10 seconds.
The value "0" means that no cyclic
sending is carried out.
Limiting values
Inactive
1 Limiting value active
2 Limiting values active
3 Limiting values active
4 Limiting values active
Here you can set whether and how
many limiting values are activated for
the CO
2
measurement.
Behaviour of the limiting
value 1 and 2 in
frost/heat protection
mode of the controller,
Operating mode heating
and
operating mode cooling
No action
send ON
send OFF
ON, no telegram
OFF, no telegram
The values can be set separately
according to heating operating mode,
cooling operating mode for the limiting
values 1 and 2.
If the controller changes to the operating
mode frost/heat protection, then the
behaviour of the limiting values
parameterised here is executed in
frost/heat protection mode according to
the operating mode of the controller.
In the "no action" setting, the behaviour
of all limiting values of the measured
value is unaffected and they continue
Page 114 of 171
Software "KNX CO2 sensor"
Parameters
Содержание CO2-Sensor
Страница 42: ...Order No 2104 Figure 7 CO2 concentration Page 42 of 171 Software KNX CO2 sensor Functional description...
Страница 74: ...Order No 2104 Page 74 of 171 Software KNX CO2 sensor Functional description...
Страница 165: ...Order No 2104 See channel 1 Disable Page 165 of 171 Software KNX CO2 sensor Parameters...