Order No. 2104 ..
Function:
External limiting values
Object
h
94,
97,
98,
99
Function
Teach
Name
S.CO2 limiting
value spec.1, 2, 3
,4
Type
1-bit
DPT
1,001
Flag
C, W, -,
(R)
1
Description
1-byte objects for storing the external CO
2
limiting values via a switching
object (teaching).
Alarms / messages
Function:
Dew point
Object
h
108
Function
Switching
Name
S.Dew point alarm
/
S.Dew point alarm
1
Type
1-bit
DPT
1,001
Flag
C, -, T, R
Description
1-bit output object for transmitting a dew point alarm (switching command).
Function:
Dew point
Object
h
108
Function
Value
Name
S.Dew point alarm
/
S.Dew point alarm
1
Type
1
bytes
DPT
5,001
Flag
C, -, T, R
Description
1-byte output object for transmitting a dew point alarm (value).
Function:
Dew point
Object
h
109
Function
Switching
Name
S.Dew point alarm
2
Type
1-bit
DPT
1,001
Flag
C, -, T, R
Description
1-bit output object for transmitting a dew point alarm (switching command).
Function:
Dew point
Object
h
109
Function
Value
Name
S.Dew point alarm
2
Type
1
bytes
DPT
5,001
Flag
C, -, T, R
Description
1-byte output object for transmitting a dew point alarm (value).
Function:
Temperature
Object
h
110
Function
Sensor fault
Name
S.Temperature
Type
1-bit
DPT
1,001
Flag
C, -, T, R
Description
1-bit output object for signalling a fault in the temperature sensor.
1: Each communication object can be read out. For reading, the R-flag must be set.
Page 38 of 171
Software "KNX CO2 sensor"
Object table