Order No. 2104 ..
the basic setpoint in the direction of
comfort temperature for cooling. Thus
the comfort set-temperature for cooling
is derived directly from the comfort
setpoint for heating.
The parameter is only visible in the
"Heating and cooling" operating mode (if
necessary with additional levels) and
only with relative setpoint presetting!
Deadband between
heating and cooling
(0...127) * 0.1 K
0...
20
...127
With relative setpoint presetting, the
comfort setpoint temperatures for
heating and cooling are derived from the
basic setpoint in consideration of the
adjusted Dead band. The deadband
(temperature zone for which there is
neither heating nor cooling) is the
difference between the comfort setpoint
temperatures. It is set using this
parameter.
The parameter is only visible in the
"Heating and cooling" operating mode (if
necessary with additional levels) and
only with relative setpoint presetting!
Difference between
basic and additional
levels
(-128...127) * 0.1 K
0...
20
...127
In a two stage control mode it is
necessary to determine the temperature
difference to the basic stage with which
the additional stage is to be incorporated
into the control This parameter defines
the level spacing.
The parameter can only be seen in two-
level control operation.
Transmission at
setpoint temperature
change by
(0...255) * 0.1 K; 0 =
inactive
0...
1
...255
Determines the size of the value change
required to automatically transmit the
current value via the "Setpoint
temperature" object. In the "0" setting,
the setpoint temperature is not
transmitted automatically when there is
a change.
Cyclical transmission of
setpoint temperature
(0...255) * 1 min;
0 = inactive
0
...255
This parameter determines whether the
setpoint temperature is to be transmitted
periodically via the "Setpoint
temperature" object. Definition of the
cycle time by this parameter In the "0"
setting, the setpoint temperature is not
transmitted automatically cyclically.
Page 138 of 171
Software "KNX CO2 sensor"
Parameters