Order No. 2104 ..
Object for additional PWM heating command value output and combined valve PWM
additional heating/cooling
Function:
Command value
Object
h
46
Function
PWM command value for
heating / PWM command
value, basic heating
Name
C.Output
Type
1
bytes
DPT
5,001
Flag
C, -, T, (R)
1
Description
1-byte object to output the internal continuous command value of a PWM
controller of the heating mode. In two-level heating mode, command value
output for the basic heating. This object is only available in this way if the type
of feedback control is configured to "Switching PI control (PWM)". In addition
to the switching 1 bit command value of the PWM, the calculated continuous
command value of the controller can also be transmitted to the bus and
displayed, e.g. in a visualisation.
Function:
Command value
Object
h
46
Function
PWM command value for
heating/cooling / PWM
command value, basic level
Name
C.Output
Type
1
bytes
DPT
5,001
Flag
C, -, T, (R)
1
Description
1-byte object to output the combined continuous command value of a PWM
controller of the heating and cooling mode. In two-level heating/cooling mode,
command value output for the basic level This object is only available in this
way if the command values for heating and cooling mode are output to a
shared object (parameter-dependent). The type of feedback control must also
be configured to "Switching PI control (PWM)". In addition to the switching 1
bit command value of the PWM, the calculated continuous command value of
the controller can also be transmitted to the bus and displayed, e.g. in a
visualisation.
Object for additional command value output, PWM additional heating and combined
valve PWM additional heating/cooling
Function:
Command value
Object
h
47
Function
PWM com. value, add.
heating
Name
C.Output
Type
1
bytes
DPT
5,001
Flag
C, -, T, (R)
1
Description
1-byte object to output the internal continuous command value of a PWM
controller for additional heating in two-level operation. This object is only
available in this way if the type of feedback control is configured to
"Continuous PI control". In addition to the switching 1 bit command value of
the PWM, the calculated continuous command value of the controller can also
be transmitted to the bus and displayed, e.g. in a visualisation.
1: Each communication object can be read out. For reading, the R-flag must be set.
Page 32 of 171
Software "KNX CO2 sensor"
Object table
Содержание CO2-Sensor
Страница 42: ...Order No 2104 Figure 7 CO2 concentration Page 42 of 171 Software KNX CO2 sensor Functional description...
Страница 74: ...Order No 2104 Page 74 of 171 Software KNX CO2 sensor Functional description...
Страница 165: ...Order No 2104 See channel 1 Disable Page 165 of 171 Software KNX CO2 sensor Parameters...