Order No. 2104 ..
This parameter is only visible with
relative setpoint presetting!
Modification of the basic
temperature setpoint
value
deactivated
approve via bus
Here, it is possible to specify if it is
possible to change the basic setpoint via
the bus.
This parameter is only visible with
relative setpoint presetting!
Accept modification of
the basic temperature
setpoint value
permanently
No
Yes
One has to distinguish between two
cases, defined by this parameter, if the
basic setpoint has been modified via the
object. This parameter is only visible
with relative setpoint presetting!
When set to "Yes": If, with this setting,
the temperature setpoint is adjusted, the
controller saves the value permanently
to the EEPROM (permanent storage).
The newly adjusted value will overwrite
the initial value, i.e. the basic
temperature originally configured via the
ETS after a reset! The changed values
are also retained after a device reset,
after a switch-over of the operating
mode or after a switch-over of the
heating/cooling mode.
With this setting, it should be noted that
frequent changing of the basic
temperature (e.g. several times a day
because of cyclical telegrams) can affect
the product life of the device as the non-
volatile storage is designed for less
frequent write access.
When set to "No": The setpoints
received via the objects remain active
only temporarily. In case of a bus
voltage failure, after a switchover to
another operating mode (e.g. Comfort to
Standby, or also Comfort to Comfort), or
after a switchover of the heating/cooling
mode (e.g. Heating to Cooling), the last
setpoint changed will be discarded and
replaced by the initial value.
Accept modification of
the setpoint
permanently?
No
Yes
One has to distinguish between two
cases, defined by this parameter, if the
setpoint has been modified via the
object. This parameter is only visible
with absolute setpoint presetting!
When set to "Yes": If, with this setting,
the temperature setpoint is adjusted, the
controller saves the value permanently
to the EEPROM (permanent storage).
Page 135 of 171
Software "KNX CO2 sensor"
Parameters
Содержание CO2-Sensor
Страница 42: ...Order No 2104 Figure 7 CO2 concentration Page 42 of 171 Software KNX CO2 sensor Functional description...
Страница 74: ...Order No 2104 Page 74 of 171 Software KNX CO2 sensor Functional description...
Страница 165: ...Order No 2104 See channel 1 Disable Page 165 of 171 Software KNX CO2 sensor Parameters...