Order No. 2104 ..
status, Presence status) are not
effected. Frequent changing of the
operating mode (e. g. several times a
day) during running operation can
adversely affect the life of the device as
the read-only memory (EEPROM) used
has been designed for less frequent
write access events only.
Frost/heat protection
Automatic frost protection
via window status
Here it is possible to determine how the
room temperature regulator switches
into the frost/heat protection.
With "automatic frost protection": the
automatic frost protection is activated.
Depending on the room temperature this
allows an automatic switch-over into the
frost protection mode.
With "Via window status": switch-over
into the frost/heat protection takes place
via the "window status" object.
Automatic frost
protection temperature
drop
Off
0.2 K / min.
0.3 K / min.
0.4 K / min.
0.5 K / min.
0.6 K / min.
This parameter determines the decrease
temperature by which the room
temperature has to decrease within one
minute in order for the controller to
switch into the frost protection mode.
The "OFF" setting will deactivate the
frost protection automatic.
Only visible if "frost/heat protection =
Automatic frost protection"!
Frost protection period
in automatic mode
(1...255) * 1 min
1...
20
...255
The length of the automatic frost
protection is defined here. After the
preset time has elapsed, the controller
will return to the operating mode which
was set before frost protection. Re-
triggering will not be possible.
Only visible if "frost/heat protection =
Automatic frost protection"!
Window status delay
(0...255) * 1 min.;
0 = inactive
0
...255
This parameter defines the delay time
for the window status. After the
parameterised time has elapsed after
the window is opened the window status
will be changed and thus the frost/heat
protection mode activated. Such delay
can make sense if short ventilation of
the room by opening the window is not
supposed to change the operating
mode.
Only visible if "Frost/heat protection =
via window status"!
h
Room temperature control -> Controller general -> Command value and status output
Page 128 of 171
Software "KNX CO2 sensor"
Parameters