Order No. 2104 ..
Objects for heating / cooling signal functions
Function:
Status signal
Object
h
37
Function
Heating indication
Name
C.Output
Type
1-bit
DPT
1,001
Flag
C, -, T, (R)
1
Description
1-bit object for the controller to report a request for heating energy. Object
value = "1": energy request, object value = "0": no energy request.
Function:
Status signal
Object
h
38
Function
Cooling indication
Name
C.Output
Type
1-bit
DPT
1,001
Flag
C, -, T, (R)
1
Description
1-bit object for the controller to report a request for cooling energy. Object
value = "1": energy request, object value = "0": no energy request.
Objects for controller disabling functions
Function:
Disabling function (room temperature regulator)
Object
h
40
Function
Disable controller
Name
C.Input
Type
1-bit
DPT
1,001
Flag
C, W, -, (R)
1
Description
1-bit object for deactivating the controller (activating dew point operation).
Polarity: Controller deactivated = "1", controller activated = "0".
Function:
Disabling function (room temperature regulator)
Object
h
41
Function
Disable additional level
2
Name
C.Input
Type
1-bit
DPT
1,001
Flag
C, W, -,
(R)
1
Description
1-bit object for deactivating the additional level of the controller. Polarity:
Additional level deactivated = "1", additional level activated = "0". This object is
only available in this way if two-level heating or cooling operation is
configured.
Objects for command value output for heating
Function:
Command value
Object
h
42
Function
Command value for heating /
command value, basic
heating
Name
C.Output
Type
1
bytes
DPT
5,001
Flag
C, -, T, (R)
1
Description
1-byte object to output the continuous command value of the heating mode. In
two-level heating mode, command value output for the basic heating. This
object is only available in this way if the type of feedback control is configured
to "Continuous PI control".
1: Each communication object can be read out. For reading, the R-flag must be set.
2: This object is only visible with activated additional stage.
Page 27 of 171
Software "KNX CO2 sensor"
Object table
Содержание CO2-Sensor
Страница 42: ...Order No 2104 Figure 7 CO2 concentration Page 42 of 171 Software KNX CO2 sensor Functional description...
Страница 74: ...Order No 2104 Page 74 of 171 Software KNX CO2 sensor Functional description...
Страница 165: ...Order No 2104 See channel 1 Disable Page 165 of 171 Software KNX CO2 sensor Parameters...