Order No. 2104 ..
Figure 27: Operating mode change-over through 4 x 1-bit objects with presence detector
object
Frost-/
Heat
protection
object
Comfo-
rt
mode
object
Standb-
y
mode
obje-
ct
Night
mode
object
Windo-
w
status
Pres-
ence
butto-
n
Pres-
ence
detecto-
r
Operation
mode
1
X
X
X
0
0
-
Frost/heat protection
0
1
X
X
0
0
-
Comfort
mode
0
0
1
X
0
0
-
Standby mode
0
0
0
1
0
0
-
Night operation
0
0
0
0
0
0
-
no change / last
state
X
X
X
X
1
X
-
Frost/heat protection
1
X
X
X
0
1
-
Comfort extension
0
1
X
X
0
1
-
Comfort
mode
0
0
1
X
0
1
-
Comfort
mode
0
0
0
1
0
1
-
Comfort extension
0
0
0
0
0
1
-
Comfort
mode-/ extension *
1
X
X
X
0
-
0
Frost/heat protection
0
1
X
X
0
-
0
Comfort
mode
0
0
1
X
0
-
0
Standby mode
0
0
0
1
0
-
0
Night operation
0
0
0
0
0
-
0
no change / last
state
X
X
X
X
1
-
X
Frost/heat protection
Page 80 of 171
Software "KNX CO2 sensor"
Functional description
Содержание CO2-Sensor
Страница 42: ...Order No 2104 Figure 7 CO2 concentration Page 42 of 171 Software KNX CO2 sensor Functional description...
Страница 74: ...Order No 2104 Page 74 of 171 Software KNX CO2 sensor Functional description...
Страница 165: ...Order No 2104 See channel 1 Disable Page 165 of 171 Software KNX CO2 sensor Parameters...