Order No. 2104 ..
4.2.4.2.8 Response to bus voltage return
It is possible to specify separately for each input whether or which reaction should take place
after bus voltage return. This means that a defined telegram can be transmitted to the bus
according to the input signal or with forced control.
The configured "Delay after reset or bus voltage return" must first have elapsed before the pre-
set reaction is executed!
Within the delay, any pending edges or signals at the inputs are not evaluated and are
discarded. The delay time is configured generally for all the inputs.
A general telegram rate limit is configurable. In this case, no telegram is transmitted within the
first 17 s after bus voltage return.
It should be noted that the configured "Delay after bus voltage return" is also active during this
time and the configured behaviour is not executed after bus voltage return if the delay time
elapses within the first 17 seconds!
i
The communication objects of the room temperature controller function, sensor, limiting
values and logic gates are independent of the configured delay time.
i
The option "transmit current input state" of the button functions "switching" and "value
transmitter" for the behaviour after bus voltage return evaluates an open switching contact
as a falling edge and a closed switching contact as a rising edge. The current input state of
the input is transmitted according to the configuration for the rising or falling edge.
Page 52 of 171
Software "KNX CO2 sensor"
Functional description