Order No. 2104 ..
60 min
Switch-off delay for
internal limiting value
object
none
1s
3s
5s
10s
15s
30s
1min
3 min
5 min
10 min
15 min
30 min
60 min
The state "0" of the limiting value is first
transferred to the limiting value object
after changing from "1" to "0" according
to the time set here.
Transmission on
change of the limiting
value object
Yes
No
With "No" the limiting value object is not
transmitted following a change.
With "Yes" the limiting value object is
transmitted following a change from "0"
to "1" or from "1" to "0".
Cyclical transmission of
the limiting value object
(0...120) * 10 s;
0 = inactive
0
...120
Here you can set whether and within
which time interval the limiting value is
transmitted. The set value multiplied by
10 is the repeat time in seconds. It is
thus possible to set the cycle time in
step widths of 10 seconds.
The value "0" indicates that the limiting
value object is not transmitted cyclically.
h
Sensor -> Dew point
Transmit on dew point
change by
(Transmission delay:
10 s)
inactive
0.5%
1%
3%
10%
So as not to burden the bus with very
frequent telegrams, the measured value
should not be sent for every tiny change.
While taking the measurement task into
account, a maximum possible value
should be set here.
The setting here refers to the measuring
range of the temperature measurement
of the dew point alarm
(-30 °C ... +70 °C -> 100 °C).
Cyclic transmission of
the dew point
temperature
(0...120) * 10 s;
0 = inactive
0
...120
Here you can set whether and within
which time interval the dew point
temperature calculated by the device is
transmitted. The set value multiplied by
10 is the repeat time in seconds. It is
thus possible to set the cycle time in
step widths of 10 seconds.
The value "0" indicates that the
temperature value is not transmitted
cyclically.
Page 123 of 171
Software "KNX CO2 sensor"
Parameters