Order No. 2104 ..
03
00
0
1
-
Comfort ex-
tension
04
00
0
1
-
Comfort ex-
tension
01
00
0
-
0
Comfort mode
02
00
0
-
0
Standby mode
03
00
0
-
0
Night operation
04
00
0
-
0
Frost/heat protection
X
00
0
-
1
Comfort mode
X
00
1
-
X
Frost/heat protection
X
00
1
X
-
Frost/heat protection
X
01
X
X
X
Comfort mode
X
02
X
X
X
Standby mode
X
03
X
X
X
Night operation
X
04
X
X
X
Frost/heat protection
Table 6: Status of the communication objects and the resulting operating mode
X: Status irrelevant
-: Not possible
i
When changing over the operating mode, the KNX change-over object is updated by the
controller and can be read out if the "Read" flag is set. If the "Transmit" flag has been set
for this object the current value will, in addition, be automatically transmitted to the bus
when it is changed.
After a device reset, the value corresponding to the set operating mode will be actively
transmitted to the bus if the "Transmit" flag has been set.
i
In parameterisation of a presence button: the presence object will be active ("1") for the
period of an active comfort extension. The presence object will be automatically deleted
("0") if the comfort extension is stopped after the extension time has elapsed, or if the
operating mode has been changed by a higher-priority operation through the change-over
objects or by local control or a forced operating mode is deactivated by the KNX forced
object (forced object -> "00"). The controller therefore automatically resets the status of the
presence button when an object value is received via the operating mode objects or the
forced object is reset.
Page 83 of 171
Software "KNX CO2 sensor"
Functional description
Содержание CO2-Sensor
Страница 42: ...Order No 2104 Figure 7 CO2 concentration Page 42 of 171 Software KNX CO2 sensor Functional description...
Страница 74: ...Order No 2104 Page 74 of 171 Software KNX CO2 sensor Functional description...
Страница 165: ...Order No 2104 See channel 1 Disable Page 165 of 171 Software KNX CO2 sensor Parameters...