Order No. 2104 ..
Function:
Command value
Object
h
42
Function
Command value for heating
(PWM) / command value,
basic heating (PWM)
Name
C.Output
Type
1-bit
DPT
1,001
Flag
C, -, T, (R)
1
Description
1-bit object to output the PWM command value of the heating mode. In two-
level heating mode, command value output for the basic heating. This object is
only available in this way if the type of feedback control is configured to
"Switching PI control (PWM)".
Function:
Command value
Object
h
42
Function
Command value for heating /
command value, basic
heating
Name
C.Output
Type
1-bit
DPT
1,001
Flag
C, -, T, (R)
1
Description
1-bit object to output the switching command value of the heating mode. In
two-level heating mode, command value output for the basic heating. This
object is only available in this way if the type of feedback control is configured
to "Switching 2-point feedback control".
Object for heating command value output and combined valve heating/cooling
Function:
Command value
Object
h
42
Function
Command value for
heating/cooling / basic level
Name
C.Output
Type
1
bytes
DPT
5,001
Flag
C, -, T, (R)
1
Description
1-byte object to output the combined continuous command value of the
heating and cooling mode. In two-level heating/cooling mode, command value
output for the basic level This object is only available in this way if the
command values for heating and cooling mode are output to a shared object
(parameter-dependent). The type of feedback control must also be configured
to "Continuous PI control".
Function:
Command value
Object
h
42
Function
Command value for
heating/cooling (PWM) /
basic level (PWM)
Name
C.Output
Type
1-bit
DPT
1,001
Flag
C, -, T, (R)
1
Description
1-bit object to output the combined PWM command value of the heating and
cooling mode. In two-level heating/cooling mode, command value output for
the basic level This object is only available in this way if the command values
for heating and cooling mode are output to a shared object (parameter-
dependent). The type of feedback control must also be configured to
"Switching PI control (PWM)".
1: Each communication object can be read out. For reading, the R-flag must be set.
Page 28 of 171
Software "KNX CO2 sensor"