Order No. 2104 ..
3 %
1.5 %
the set operation.
Time between switching
and dimming,
Base
130 ms
260 ms
520 ms
1 sec
Time from which the dimming function
("long press") is executed.
Time = Basic x Factor
Time between switching
and dimming,
Factor (4...127)
4
...127
Time from which the dimming function
("long press") is executed.
Time = Basic x Factor
Presetting: 130 ms × 4 = 520 ms
Send stop telegram ?
Yes
No
One or no telegram is transmitted on
releasing a pushbutton at the input
(falling edge).
Telegram
repeat?
Yes
No
Cyclical repetition of telegrams during a
long press.
Time between two
telegrams,
Base
130 ms
260 ms
520 ms
1 sec
Time between two telegrams when
telegram repetition is active. A new
dimming telegram is transmitted after
this time has elapsed.
Only if telegram repetition ? = "YES".
Time = Basic x Factor
Time between two
telegrams,
Factor (3...127)
3...
10
...127
Time between two telegrams when
telegram repetition is active. A new
dimming telegram is transmitted after
this time has elapsed.
Only if telegram repetition ? = "YES".
Time = Basic x Factor
Presetting: 130 ms × 10 = 1.3 s
Behaviour after bus
voltage
return
no reaction
Send ON telegram
Send OFF telegram
It is possible to specify which reaction
should take place after bus voltage
return. The configured delay time after
reset or bus voltage return must first
have elapsed before the pre-set reaction
is executed here.
With "no reaction", no reaction occurs.
With "transmit ON telegram" an "ON" is
transmitted.
With "transmit OFF telegram" an "OFF"
is transmitted.
Page 146 of 171
Software "KNX CO2 sensor"
Parameters