Order No. 2104 ..
Figure 37: Setpoint temperatures in the operating mode "Basic and additional heating and
cooling" with asymmetrical deadband
T
Comfort setpoint add. level Heating
≤ T
Comfort setpoint basic level Heating
≤ T
Comfort setpoint basic level Cooling
≤ T
Comfort
setpoint add. level Cooling
T
Standby setpoint add. level Heating
≤ T
Standby setpoint basic level Heating
≤ T
Standby setpoint basic level Cooling
≤ T
Standby
setpoint add. level Cooling
T
Standby setpoint heating
≤ T
Comfort setpoint heating
≤ T
Comfort setpoint cooling
≤ T
Standby setpoint cooling
or
T
Comfort setpoint add. level Heating
≤ T
Comfort setpoint basic level Heating
≤ T
Comfort setpoint basic level Cooling
≤ T
Comfort
setpoint add. level Cooling
T
Night setpoint add. level Heating
≤ T
Night setpoint basic level Heating
≤ T
Night setpoint basic level Cooling
≤ T
Night setpoint add. level
Cooling
T
Night setpoint heating
≤ T
Comfort setpoint heating
≤ T
Comfort setpoint cooling
≤ T
Night setpoint cooling
deadband and deadband positions in the combined heating and cooling operating mode
With relative setpoint presetting, the comfort setpoint temperatures for heating and cooling are
derived from the basic setpoint in consideration of the adjusted Dead band. The deadband
(temperature zone for which there is neither heating nor cooling) is the difference between the
comfort setpoint temperatures. This deadband does not exist for absolute setpoint presetting.
Page 94 of 171
Software "KNX CO2 sensor"
Functional description