Order No. 2104 ..
value, e.g. by .button-press.
Activation of limiting
value 1 or 2
(LV = Limiting value,
Hyst = Hysteresis)
Exceed LV=ON,
undershoot LV-hyst.=OFF
Exceed LV=OFF,
Undershoot LV-hyst.=ON
Undershoot LV=ON,
exceed LV-hyst.=OFF
Undershoot LV=OFF,
exceed LV-hyst.=ON
Exceed LV=ON,
undershoot LV-hyst.=no
telegram
Exceed LV=OFF,
Undershoot LV-hyst.=no
telegram
Undershoot LV=ON,
exceed LV-hyst.=no
telegram
Undershoot LV=OFF,
exceed LV-hyst.=no
telegram
Exceed LV-hyst.=no
telegram, undershoot LV-
hyst.=OFF
Exceed LV-hyst.=no
telegram, undershoot LV-
hyst.=ON
Undershoot LV-hyst.=no
telegram, exceed LV-
hyst.=OFF
Undershoot LV-hyst.=no
telegram, exceed LV-
hyst.=ON
Determines in which case the limiting
values are activated.
Switch-on delay for
internal limiting value
object
none
1s
3s
5s
10s
15s
30s
1min
3 min
5 min
10 min
15 min
30 min
The state "1" of the limiting value is first
transferred to the limiting value object
after changing from "0" to "1" according
to the time set here.
Page 122 of 171
Software "KNX CO2 sensor"
Parameters