Order No. 2104 ..
Upward adjustment of
the basic setpoint
temperature
(0...10) * 1 K
0 K
+ 1 K
+ 2 K
+ 3 K
+ 4 K
+ 5 K
+ 8 K
+ 9 K
+ 10 K
This is used to define the maximum
range in which the basic setpoint
temperature can be adjusted upwards.
This parameter is only visible with
relative setpoint presetting!
Downward adjustment
of the basic setpoint
temperature
(0...10) * 1 K
0 K
- 1 K
- 2 K
- 3 K
- 4 K
- 5 K
- 8 K
- 9 K
- 10 K
This is used to define the maximum
range in which the basic setpoint
temperature can be adjusted
downwards.
This parameter is only visible with
relative setpoint presetting!
Lower the setpoint
temperature during
standby operation
(heating)
(-128...0) * 0.1 K
-128...
-20
...0
The value by which the standby setpoint
temperature for heating is lowered
compared to the heating comfort
temperature.
The parameter is only visible in the
"Heating" or "Heating and cooling"
operating mode (if necessary with
additional levels) and only with relative
setpoint presetting.
Lower the setpoint
temperature during
night operation
(heating)
(-128...0) * 0.1 K
-128...
-40
...0
The value by which the night setpoint
temperature for heating is lowered
compared to the heating comfort
temperature.
The parameter is only visible in the
"Heating" or "Heating and cooling"
operating mode (if necessary with
additional levels) and only with relative
setpoint presetting.
Raise the setpoint
temperature during
standby operation
(cooling)
(0...127) * 0.1 K
0...
20
...127
The value by which the standby setpoint
temperature for cooling is lowered
compared to the cooling comfort
temperature.
The parameter is only visible in the
"Heating" or "Heating and cooling"
operating mode (if necessary with
additional levels) and only with relative
setpoint presetting.
Raise the setpoint
temperature during
night operation (cooling)
(0...127) * 0.1 K
0...
40
...127
The value by which the night
temperature for cooling is lowered
compared to the cooling comfort
temperature.
Page 139 of 171
Software "KNX CO2 sensor"
Parameters
Содержание CO2-Sensor
Страница 42: ...Order No 2104 Figure 7 CO2 concentration Page 42 of 171 Software KNX CO2 sensor Functional description...
Страница 74: ...Order No 2104 Page 74 of 171 Software KNX CO2 sensor Functional description...
Страница 165: ...Order No 2104 See channel 1 Disable Page 165 of 171 Software KNX CO2 sensor Parameters...