CI Series QuickStart Guide
Compact Infrared Sensor
Use this QuickStart Guide for quick and easy mechanical
installation, electrical wiring, and operation of the CI Series sensor.
Mechanical Installation
The CI Series sensors consist of the following components:
■
C1 sensor
■
2 mounting nuts
■
1m (3ft) cable
Mounting Preparation
The CI sensor must be securely mounted to a vibration-free,
mechanically stable support, away from motors producing large
step-load changes.
To prepare for sensor mounting:
■
Select a mounting location that ensures the spot size is
the same or smaller than the target.
■
Cut a 19mm (.75in) hole in the panel.
■
Determine if you need Raytek® air purge or air/water
cooing accessories.
When operating the CI sensor in ambient temperatures
exceeding 70˚C (160˚F), water cooling is required.
■
If needed, attach accessories to the sensor.
■
Have a 12-24 VDC 10mA power supply available.
Mounting the Sensor
To mount the sensor:
■
Screw 1 nut onto the sensor until it is more than halfway from
the lens.
■
Insert the sensor into the panel hole and screw on the 2nd nut.
■
Aim sensor and tighten both nuts until sensor is secure.
Electrical Installation
There are three types of CI sensors. Each sensor (J Thermocouple,
K Thermocouple, or the 10mV/˚C Voltage) has a different wire color
system. Use one of the following charts specific to your sensor as
a wiring guide.
Wiring
There is a 4-wire, PVC
cable attached to the
sensor. The cable holds
two pairs of wires and a
bare shield (
ground
) wire.
Standard Wiring
Wire
Label Number Function
Wire Color
Output 1
(Iron)
White
2 Signal –
(Constantan)
Red
(White Stripe)
Power 3
Power Red
(Yellow Stripe)
Supply 4
Power Supply – Yellow
– 5
Shield Ground
Bare
HigH tEMPEratUrE CaBLE Wiring
Output 1
(Iron)
White
2 Signal –
(Constantan)
Red
(White Stripe)
Power 3
Power Red
Supply 4
Power Supply – Yellow
– 5
Shield Ground
Bare
J-TYPE THERMOCOUPLE
Standard Wiring
Wire
Label Number Function
Wire Color
Output 1 (
Chromel
) Yellow
2 Signal – (
Alumel
)
Red (
Yellow Stripe
)
Power 3
Power Red (
White Stripe
)
Supply 4
Power Supply – White
– 5
Shield Ground
Bare
HIGH TEMPERATURE CABLE WIRING
Output 1 (
Chromel
) Yellow
2 Signal – (
Alumel
)
Red
Power 3
Power Red (
White Stripe
)
Supply 4
Power Supply – White
– 5
Shield Ground
Bare
Standard Wiring
Wire
Label Number Function
Wire Color
Output 1
White
2 Signal –
Green
Power 3
Power Red
Supply 4
Power Supply – Black
– 5
Shield Ground
Bare
HIGH TEMPERATURE CABLE WIRING
Output 1
Red
2 Signal –
Yellow
Power 3
Power Red (
White Stripe
)
Supply 4
Power Supply – White
– 5
Shield Ground
Bare
K-TYPE THERMOCOUPLE
10mV/˚C VOLTAGE
WARNING
INCORRECT WIRING WILL CAUSE SEVERE ANd
PERMANENT dAMAGE TO THE SENSOR
12 - 24 VDC Red (+)
1
2
3
4
5
(Shield)
LABEL IS ON POWER
SUPPLY WIRES ONLY
Wire Numbers
(Refer to the chart)
USE CHART SPECIFIC TO YOUR SENSOR FOR
STANdARd OR HIGH TEMPERATURE CABLE WIRING