![Fuji Electric FRENIC-MEGA Скачать руководство пользователя страница 62](http://html1.mh-extra.com/html/fuji-electric/frenic-mega/frenic-mega_instruction-manual_2341853062.webp)
3-5
(2) When function code E45 (LCD monitor item selection) is set at "1"
The LCD monitor displays the output frequency, output current, and calculated torque in a bar chart.
(The upper indicators show the unit of values displayed on the LED monitor as detailed in Section 3.3.2. The lower ones show
the running status and run command source.)
The full scale (maximum value) for each parameter is as follows:
Output frequency: Maximum frequency
Output current:
200% of inverter’s rated current
Calculated torque: 200% of rated torque generated by motor
Figure 3.4 Bar Chart
3.3.2 Monitoring the running status on the LED monitor
The items listed below can be monitored on the 7-segment LED monitor. Immediately after the power is turned ON, the monitor
item specified by function code E43 is displayed.
Pressing the
key in Running mode switches between monitor items in the sequence shown in Table 3.4. The "Monitor page #"
column shows the monitor page of the items supported.
Table 3.4 Items Monitored
Monitored Items on the
LED Monitor
Example Unit
Meaning
of
Displayed
Value
Function
code E43
Monitor page #
Speed Monitor
Function code E48 specifies what to be displayed.
0
0
Output frequency 1
(before slip
compensation)
5*00
Hz
Frequency actually being output (Hz)
(E48 = 0)
Output frequency 2
(after slip compensation)
5*00
Hz
Frequency actually being output (Hz)
(E48 = 1)
Reference
frequency
5*00
Hz
Frequency actually being specified (Hz)
(E48 = 2)
Motor speed
1500
r/min
P01
120
×
(Hz)
frequency
Output
(E48 = 3)
Load shaft speed
30*0
r/min
Output frequency (Hz) x E50
(E48 = 4)
Line
speed
30*0
m/min Output frequency (Hz) x E50
(E48 = 5)
Display speed (%)
5*0
%
100
×
(Hz)
frequency
Maximum
(Hz)
frequency
Output
(E48 = 7)
Output current
1"34
A
Current output from the inverter in RMS
3
8
Input power
1*25
kW
Input power to the inverter
9
9
Calculated torque
50
%
Motor output torque in %
(Calculated value)
8 10
Output voltage
200
V
Voltage output from the inverter in RMS
4
11
Motor output
)85
kW
Motor output in kW
16
12
Load factor
50
%
Load factor of the motor in % as the rated
output being at 100%
15 13
Output frequency
Output current
Bar chart
Calculated torque
Содержание FRENIC-MEGA
Страница 36: ...2 6 Unit inch mm Refer to Section 2 3 3 9...
Страница 208: ...5 89 Examples of Sequence Circuits 1 Standard sequence 2 Sequence with an emergency switching function...
Страница 356: ...MEMO...
Страница 358: ...Fuji Electric Co Ltd Fuji Electric Corp of America http www fujielectric com fecoa 2011 04 D11 D10...