Allowable average loss (F51)
The allowable average loss refers to a tolerance for motor continuous operation, which is obtained based on the %ED (%)
and motor rated capacity (HP).
Data for F51
Function
0.001 to 99.99
0.001 to 99.99 (kW)
During deceleration:
Allowable average loss (kW) =
2
×
Motor rated capacity (HP)
×
0.75
100
%ED(%)
Expression (3)
During constant speed operation:
Allowable average loss (kW) =
×
Motor rated capacity (HP)
×
0.75
100
%ED(%)
Expression (4)
Resistance (F52)
F52 specifies the resistance of the braking resistor.
F80
Switching between LD, MD and HD drive modes
F80 specifies whether to drive the inverter in the low duty (LD), medium duty (MD), or high duty (HD) mode.
To change the F80 data, it is necessary to press the"
+
keys" or "
+
keys" (simultaneous keying).
F80 data
Drive mode
Application
Continuous rated current level
Overload
capability
Maximum
frequency
1
LD (Low Duty)
mode
Light load
Drive a motor whose capacity is the same
as the inverter's one.
120% for 1 min.
120 Hz
2
MD (Medium
Duty) mode
Medium load
Drives a motor whose capacity is the
same as the inverter's one or derates a
motor one rank lower than the inverter's
capacity.
150% for 1 min.
120 Hz
0
HD (High Duty)
mode
Heavy load
Derates a motor one or two ranks lower
than the inverter's capacity.
150% for 1 min.
200% for 3 s
500 Hz
Switching to the MD/HD mode increases the overload capability (%) against the continuous current level up to 150%, but it
requires derating the motor one or two ranks lower than the inverter's capacity.
Note: For 7.5 HP or smaller, when LD mode is selected, the HD mode specification applies.
For the rated current level, see Chapter 8 "SPECIFICATIONS."
Содержание FRENIC-MEGA
Страница 36: ...2 6 Unit inch mm Refer to Section 2 3 3 9...
Страница 208: ...5 89 Examples of Sequence Circuits 1 Standard sequence 2 Sequence with an emergency switching function...
Страница 356: ...MEMO...
Страница 358: ...Fuji Electric Co Ltd Fuji Electric Corp of America http www fujielectric com fecoa 2011 04 D11 D10...