![Fuji Electric FRENIC-MEGA Скачать руководство пользователя страница 215](http://html1.mh-extra.com/html/fuji-electric/frenic-mega/frenic-mega_instruction-manual_2341853215.webp)
5-96
Ch
ap
. 5
FUNCTION C
O
DES
E codes
E30 Frequency
Arrival
(Hysteresis
width)
E30 specifies the detection level (hysteresis width) for the "Frequency (speed) arrival signal"
FAR
and the "Frequency
(speed) arrival signal 3"
FAR3
.
Output signal
Data assigned to
output terminal
Operating condition 1
Operating condition 2
Frequency (speed)
arrival signal
FAR
1
Both signals come ON when the
difference between the output
frequency (estimated/detected
speed) and the reference frequency
(reference speed) comes within the
frequency arrival hysteresis width
specified by E30.
FAR
always goes OFF when the run
command is OFF or the reference speed
is "0."
Frequency (speed)
arrival signal 3
FAR3
72
When the run command is OFF, the
inverter regards the reference speed as
"0," so
FAR3
comes ON as long as the
output frequency (estimated/detected
speed) is within the range of "0 ± the
frequency arrival hysteresis width
specified by E30."
- Data setting range: 0.0 to 10.0 (Hz)
The operation timings of each signal are shown below.
E31, E32
Frequency Detection (Level and Hysteresis width)
E36, E54 (Frequency Detection 2 and 3 (Level))
When the output frequency (estimated/detected speed) exceeds the frequency detection level specified by E31, the
"Frequency (speed) detected signal" comes ON; when it drops below the "Frequency detection level minus Hysteresis width
specified by E32," it goes OFF.
The following three settings are available.
Output signal
Data assigned to
output terminal
Operation level
Hysteresis width
Range: 0.0 to 500.0 Hz Range: 0.0 to 500.0 Hz
Frequency (speed)
detected signal
FDT
2 E31
E32
Frequency (speed)
detected signal 2
FDT2
31 E36
Frequency (speed)
detected signal 3
FDT3
58 E54
Содержание FRENIC-MEGA
Страница 36: ...2 6 Unit inch mm Refer to Section 2 3 3 9...
Страница 208: ...5 89 Examples of Sequence Circuits 1 Standard sequence 2 Sequence with an emergency switching function...
Страница 356: ...MEMO...
Страница 358: ...Fuji Electric Co Ltd Fuji Electric Corp of America http www fujielectric com fecoa 2011 04 D11 D10...