5-21
Code Name
Data
setting
range
Ch
ange wh
e
n
ru
nnin
g
Dat
a
cop
yi
ng
Default
setting
Drive control
Refer
to
page:
V/f
PG
V/f
w/o
PG
w/
PG
Torque
control
r28
(Iron loss factor 2) 0.00% to 20.00%
Y Y1
Y2 0.00 Y Y Y Y Y
―
r29
(Iron loss factor 3) 0.00% to 20.00%
Y Y1
Y2 0.00 Y Y Y Y Y
r30
(Magnetic saturation factor 1) 0.0% to 300.0%
Y Y1
Y2
*7 Y Y Y Y Y
r31
(Magnetic saturation factor 2) 0.0% to 300.0%
Y Y1
Y2
*7 Y Y Y Y Y
r32
(Magnetic saturation factor 3) 0.0% to 300.0%
Y Y1
Y2
*7 Y Y Y Y Y
r33
(Magnetic saturation factor 4) 0.0% to 300.0%
Y Y1
Y2
*7 Y Y Y Y Y
r34
(Magnetic saturation factor 5) 0.0% to 300.0%
Y Y1
Y2
*7 Y Y Y Y Y
r35
(Magnetic
saturation
extension
factor
"a")
0.0% to 300.0%
Y Y1
Y2
*7 Y Y Y Y Y
r36
(Magnetic
saturation
extension
factor
"b")
0.0% to 300.0%
Y Y1
Y2
*7 Y Y Y Y Y
r37
(Magnetic
saturation
extension
factor
"c")
0.0% to 300.0%
Y Y1
Y2
*7 Y Y Y Y Y
r39 Motor 4 Selection
0: Motor characteristics 0 (Fuji standard motors, 8-series)
1: Motor characteristics 1 (HP rating motors)
2: Motor characteristics 2 (Fuji motors exclusively designed
for vector control)
3: Motor characteristics 3 (Fuji standard motors, 6-series)
4: Other motors
N Y1
Y2
1 Y Y Y Y Y
r40 Slip Compensation 4
(Operating
conditions)
0: Enable during ACC/DEC and at base frequency or above
1: Disable during ACC/DEC and enable at base frequency
or above
2: Enable during ACC/DEC and disable at base frequency
or above
3: Disable during ACC/DEC and at base frequency or
above
N Y 0 Y
Y
N
N N
r41 Output Current
Fluctuation
Damping
Gain for Motor 4
0.00 to 1.00
Y Y 0.20
Y
Y
N
N N
r42 Motor/Parameter Switching 4
(Mode
selection)
0: Motor (Switch to the 4th motor)
1: Parameter (Switch to particular r codes)
N Y 0 Y
Y
Y
Y Y
5-137
r43 Speed
Control
4
(Speed command filter)
0.000 to 5.000 s
Y Y
0.020
N
Y
Y
Y N
―
r44
(Speed detection filter) 0.000 to 0.100 s
Y*
Y 0.005 N Y Y Y N
r45
P (Gain) 0.1 to 200.0 times
Y*
Y 10.0 N Y Y Y N
r46
I (Integral time) 0.001 to 9.999 s
Y*
Y 0.100 N Y Y Y N
r48
(Output filter) 0.000 to 0.100 s
Y Y
0.002
N
Y
Y
Y N
r49 (Notch filter resonance frequency) 1 to 200 Hz
Y Y 200 N
N
N
Y N
r50
(Notch filter attenuation level) 0 to 20 dB
Y Y 0 N
N
N
Y N
r51 Cumulative Motor Run Time 4
0 to 99990 hours
(The cumulative run time can be modified or reset.)
N N - Y
Y
Y
Y Y
r52 Startup Counter for Motor 4
Indication of cumulative startup count
0 to 65535 times
Y N - Y
Y
Y
Y Y
r53 Motor 4
(%X correction factor 1) 0% to 300%
Y Y1
Y2
100 Y Y Y Y Y
r54
(%X correction factor 2) 0% to 300%
Y Y1
Y2
100 Y Y Y Y Y
r55 (Torque current under vector control) 0.00 to 2000 A
N Y1
Y2
*7 N N Y Y Y
r56
(Induced voltage factor under
vector
control)
50 to 100
N Y1
Y2 85
(90)
*8
N N Y Y Y
r57 Reserved
*
9
―
- - - -
-
-
- -
*7 The motor parameters are automatically set, depending upon the inverter's capacity. See Table B.
*8 85% for inverters of 150 HP or less; 90% for those of 175 HP or above.
*9 Factory use. Do not access these function codes.