5-143
PID Command Manually Specified with
and Keys and Requirements
PID control
(Mode selection)
J01
PID control
(Remote command SV)
J02
LED monitor
E43
Multi-frequency
SS4
,
SS8
Display during
/ key operation
1 or 2
0
Other than 0
ON or OFF
PID process command by keypad
Other than 0
PID process command currently selected
3
0
PID dancer position command by keypad
Other than 0
PID dancer position command currently selected
[ 2 ] PID command by analog inputs (J02 = 1)
When any analog input (voltage input to terminals [12] and [V2], or current input to terminal [C1]) for PID command 1 (J02
= 1) is used, it is possible to arbitrary specify the PID command by multiplying the gain and adding the bias. The polarity
can be selected and the filter time constant and offset can be adjusted. In addition to J02 setting, it is necessary to select PID
command 1 for analog input (specified by any of E61 to E63, function code data = 3). For details, refer to the descriptions of
E61 to E63.
Adjustable elements of PID command
Input
terminal
Input range
Bias Gain
Polarity
Filter time
constant
Offset
Bias
Base
point
Gain
Base
point
[12]
0 to +10 V, -10 to +10V
C51 C52
C32 C34 C35 C33 C31
[C1]
4 to 20 mA
C37
C39
-
C38
C36
[V2]
0 to +10 V, -10 to +10 V
C42
C44
C45
C43
C41
Offset (C31, C36, C41)
C31, C36 or C41 configures an offset for an analog voltage/current input. The offset also applies to signals sent from the
external equipment.
Filter time constant (C33, C38, C43)
C33, C38, and C43 provide the filter time constants for the voltage and current of the analog input. Choose appropriate
values for the time constants considering the response speed of the machinery system, as large time constants slow down the
response. If the input voltage fluctuates because of noise, specify large time constants.
Polarity (C35, C45)
C35 and C45 specify the input range for analog input voltage.
Data for C35 and C45
Terminal input specifications
0
-10 to +10 V
1
0 to +10 V (negative value of voltage is regarded as 0 V)