![Fuji Electric FRENIC-MEGA Скачать руководство пользователя страница 163](http://html1.mh-extra.com/html/fuji-electric/frenic-mega/frenic-mega_instruction-manual_2341853163.webp)
5-44
Ch
ap
. 5
FUNCTION C
O
DES
F codes
Examples
:
Normal (linear) V/f pattern
V/f pattern with three non-linear points
Base Frequency 1 (F04)
Data setting range: 25.0 to 500.0 (Hz)
Set the rated frequency printed on the nameplate labeled on the motor.
Rated Voltage at Base Frequency 1 (F05)
Data setting range: 0: Output a voltage in proportion to input voltage
(The Automatic Voltage Regulator (AVR) is disabled.)
80 to 240 (V): Output an AVR-controlled voltage for 230 V series
160 to 500 (V): Output an AVR-controlled voltage for 460 V series
Set "0" or the rated voltage printed on the nameplate labeled on the motor.
- If F05 = 0, the rated voltage at base frequency is determined by the power source of the inverter. The output voltage will
fluctuate in line with the input voltage fluctuation.
- If F05 = an arbitrary value other than 0, the inverter automatically keeps the output voltage constant in line with the
setting. When any of the auto torque boost, auto energy saving, etc. is enabled, the F05 data should be equal to the rated
voltage of the motor.