9.3.2 Recommended
installation
procedure
To make the machinery or equipment fully compliant with the EMC Directive, have certified technicians wire the motor and
inverter in strict accordance with the procedure described below.
In case an EMC-compliant filter (optional) is externally used
1) Mount the inverter and the filter on a grounded panel or metal plate. Use shielded wires for the motor cable and route the
cable as short as possible. Firmly clamp the shields to the metal plate to ground them. Further, connect the shielding layers
electrically to the grounding terminal of the motor.
2) For connection to inverter's control terminals and for connection of the RS-485 communication signal cable, use shielded
wires. As with the motor, clamp the shields firmly to a grounded panel.
3) If noise from the inverter exceeds the permissible level, enclose the inverter and its peripherals within a metal panel as shown
in Figure 9.1.