![Fuji Electric FRENIC-MEGA Скачать руководство пользователя страница 181](http://html1.mh-extra.com/html/fuji-electric/frenic-mega/frenic-mega_instruction-manual_2341853181.webp)
5-62
Ch
ap
. 5
FUNCTION C
O
DES
F codes
F26, F27
Motor Sound (Carrier frequency and Tone)
H98 (Protection/Maintenance Function (Mode selection))
Motor Sound (Carrier frequency) (F26)
F26 controls the carrier frequency so as to reduce an audible noise generated by the motor or electromagnetic noise from the
inverter itself, and to decrease a leakage current from the main output (secondary) wirings.
Item Characteristics
Remarks
Carrier frequency
0.75
to 16
kHz
0.5 to 30 HP
(LD mode)
0.5 to 100 HP
(HD mode)
0.75
to 10
kHz
40 to 100 HP
(LD mode)
125 to 800 HP
(HD mode)
0.75
to 6
kHz 125 to 900 HP
(LD mode)
900 and 1000 HP (HD mode)
0.75
to 4 kHz
1000 HP
(LD mode)
0.75
to 2 kHz
150 to 800 HP
(MD mode)
Motor sound noise emission
High
↔
Low
Motor temperature
(due to harmonics components)
High
↔
Low
Ripples in output current waveform
Large
↔
Small
Leakage current
Low
↔
High
Electromagnetic noise emission
Low
↔
High
Inverter loss
Low
↔
High
Specifying a too low carrier frequency will cause the output current waveform to have a large amount of ripples.
As a result, the motor loss increases, causing the motor temperature to rise. Furthermore, the large amount of
ripples tends to cause a current limiting alarm. When the carrier frequency is set to 1 kHz or below, therefore,
reduce the load so that the inverter output current comes to be 80% or less of the rated current.
When a high carrier frequency is specified, the temperature of the inverter may rise due to a surrounding
temperature rise or an increase of the load. If it happens, the inverter automatically decreases the carrier frequency
to prevent the inverter overload alarm
0lu
. With consideration for motor noise, the automatic reduction of carrier
frequency can be disabled. Refer to the description of H98.
It is recommended to set the carrier frequency at 5 kHz or above under vector control without/with speed sensor.
DO NOT set it at 1 kHz or below.
Motor Sound (Tone) (F27)
F27 changes the motor running sound tone (only for motors under V/f control). This setting is effective when the carrier
frequency specified by function code F26 is 7 kHz or lower. Changing the tone level may reduce the high and harsh running
noise from the motor.
If the tone level is set too high, the output current may become unstable, or mechanical vibration and noise may
increase.
Also, this function code may not be very effective for certain types of motor.
Data for F27
Function
0
Disable (Tone level 0)
1
Enable (Tone level 1)
2
Enable (Tone level 2)
3
Enable (Tone level 3)