5-51
F14
Restart Mode after Momentary Power Failure (Mode selection)
H13 (Restart Mode after Momentary Power Failure (Restart time))
H14 (Restart Mode after Momentary Power Failure (Frequency fall rate))
H15 (Restart Mode after Momentary Power Failure (Continuous running level))
H16 (Restart Mode after Momentary Power Failure (Allowable momentary power failure time))
H92 (Continuity of running (P))
H93 (Continuity of running (I))
F14 specifies the action to be taken by the inverter such as trip and restart in the event of a momentary power failure.
Restart mode after momentary power failure (Mode selection) (F14)
• Under V/f control
Data for F14
Description
Auto search disabled
Auto search enabled
0: Trip immediately
As soon as the DC link bus voltage drops below the undervoltage detection level due to a
momentary power failure, the inverter issues undervoltage alarm
lu
and shuts down its output
so that the motor enters a coast-to-stop state.
1: Trip after recovery
from power failure
As soon as the DC link bus voltage drops below the undervoltage detection level due to a
momentary power failure, the inverter shuts down its output so that the motor enters a
coast-to-stop state, but it does not enter the undervoltage state or issue undervoltage alarm
lu
.
The moment the power is restored, an undervoltage alarm
lu
is issued, while the motor remains
in a coast-to-stop state.
2: Trip after
decelerate-to-stop
As soon as the DC link bus voltage drops below the continuous running level due to a
momentary power failure, decelerate-to-shop control is invoked. Decelerate-to-stop control
regenerates kinetic energy from the load's moment of inertia, slowing down the motor and
continuing the deceleration operation. After decelerate-to-stop operation, an undervoltage alarm
lu
is issued.
3: Continue to run
(for heavy inertia or
general loads)
As soon as the DC link bus voltage drops below the continuous running level due to a
momentary power failure, continuous running control is invoked. Continuous running control
regenerates kinetic energy from the load’s moment of inertia, continues running, and waits the
recovery of power. When an undervoltage condition is detected due to a lack of energy to be
regenerated, the output frequency at that time is saved, the output of the inverter is shut down,
and the motor enters a coast-to-stop state.
If a run command has been input,
restoring power restarts the inverter at
the output frequency saved when
undervoltage was detected.
If a run command has been input, restoring power
performs auto search for idling motor speed and
restarts running the motor at the frequency calculated
based on the searched speed.
This setting is ideal for fan applications with a large moment of inertia.
4: Restart at the
frequency at which
the power failure
occurred
(for general loads)
As soon as the DC link bus voltage drops below the undervoltage detection level due to a
momentary power failure, the inverter shuts down the output so that the motor enters a
coast-to-stop state.
If a run command has been input,
restoring power restarts the inverter at
the output frequency saved when
undervoltage was detected.
If a run command has been input, restoring power
performs auto search for idling motor speed and
restarts running the motor at the frequency calculated
based on the searched speed.
This setting is ideal for applications with a moment of inertia large enough not to slow down the
motor quickly, such as fans, even after the motor enters a coast-to-stop state upon occurrence of
a momentary power failure.
5: Restart at the
starting frequency
As soon as the DC link bus voltage drops below the undervoltage detection level due to a
momentary power failure, the inverter shuts down the output so that the motor enters a
coast-to-stop state.
If a run command has been input,
restoring power restarts the inverter at
the starting frequency specified by
function code F23.
If a run command has been input, restoring power
performs auto search for idling motor speed and
restarts running the motor at the frequency calculated
based on the searched speed.
This setting is ideal for heavy load applications such as pumps, having a small moment of inertia,
in which the motor speed quickly goes down to zero as soon as it enters a coast-to-stop state
upon occurrence of a momentary power failure.
Auto search is enabled by turning ON the digital terminal command
STM
("Enable auto search for idling motor speed at
starting") or setting the H09 data to "1" or "2."
For details about the digital terminal command
STM
and auto search, refer to the description of H09 (Starting Mode, Auto
search).