The following tables list the function codes available for the FRENIC-MEGA series of inverters.
F codes: Fundamental Functions
Code Name
Data
setting
range
Cha
nge when
ru
nnin
g
Da
ta
cop
yi
ng
Default
setting
Drive control
Refer
to
page:
V/f
PG
V/f
w/o
PG
w/
PG
Torque
control
F00 Data Protection
0: Disable both data protection and digital reference
protection
1: Enable data protection and disable digital reference
protection
2: Disable data protection and enable digital reference
protection
3: Enable both data protection and digital reference
protection
Y
Y
0 Y Y Y Y Y 5-34
F01 Frequency Command 1
0:
/ keys on keypad
1: Voltage input to terminal [12] (-10 to +10 VDC)
2: Current input to terminal [C1] (4 to 20 mA DC)
3: Sum of voltage and current inputs to terminals [12] and
[C1]
5: Voltage input to terminal [V2] (-10 to +10 VDC)
7: Terminal command
UP/DOWN
control
8:
/ keys on keypad
(balanceless-bumpless switching available)
11: Digital input interface card (option)
12: Pulse train input
N
Y
0 Y Y Y Y N
F02 Operation Method
0: Keypad
1: Terminal command
FWD
or
REV
2: Keypad (Forward direction)
3: Keypad
(Reverse direction)
N
Y
0 Y Y Y Y Y 5-42
F03 Maximum Frequency 1
25.0 to 500.0 Hz
N
Y 60.0 Y Y Y Y Y 5-43
F04 Base Frequency 1
25.0 to 500.0 Hz
N
Y 60.0 Y Y Y Y Y
F05 Rated Voltage at Base Frequency 1
0: Output a voltage in proportion to input
voltage
80 to 240 V: Output an AVR-controlled voltage
(for 230 V series)
160 to 500 V: Output an AVR-controlled voltage
(for 460 V series)
N
Y2
230
460
Y Y Y Y Y
F06 Maximum Output Voltage 1
80 to 240 V: Output an AVR-controlled voltage
(for 230 V series)
160 to 500 V: Output an AVR-controlled voltage
(for 460 V series)
N
Y2
230
460
Y Y N N Y
F07 Acceleration Time 1
0.00 to 6000 s
Note: Entering 0.00 cancels the acceleration time, requiring
external soft-start.
Y
Y
*1 Y Y Y Y N 5-45
F08 Deceleration Time 1
Y
Y
*1 Y Y Y Y N
F09 Torque Boost 1
0.0% to 20.0% (percentage with respect to "Rated Voltage
at Base Frequency 1")
Y
Y 0.0 Y
Y
N
N N
5-48
5-64
F10 Electronic Thermal Overload
Protection for Motor 1
(Select
motor
characteristics)
1: For a general-purpose motor with shaft-driven cooling
fan
2: For an inverter-driven motor, non-ventilated motor, or
motor with separately powered cooling fan
Y
Y
1 Y Y Y Y Y 5-49
F11
(Overload detection level) 0.00: Disable
1% to 135% of the rated current (allowable continuous drive
current) of the motor
Y
Y1
Y2
*2 Y Y Y Y Y
F12
(Thermal time constant) 0.5 to 75.0 min
Y
Y
*3 Y Y Y Y Y
F14 Restart Mode after Momentary
Power Failure
(Mode selection)
0: Trip
immediately
1: Trip after a recovery from power failure
2: Trip after decelerate-to-stop
3: Continue to run, for heavy inertia or general loads
4: Restart at the frequency at which the power failure
occurred, for general loads
5: Restart at the starting frequency
Y
Y
0 Y Y Y Y N 5-51
F15 Frequency Limiter
(High) 0.0 to 500.0 Hz
Y
Y 70.0 Y Y Y Y N 5-57
F16
(Low) 0.0 to 500.0 Hz
Y
Y 0.0 Y Y Y Y N
F18 Bias
(Frequency command 1) -100.00% to 100.00%
Y*
Y 0.00 Y Y Y Y N 5-34
5-58
F20 DC Braking 1
(Braking
starting
frequency)
0.0 to 60.0 Hz
Y
Y 0.0 Y Y Y Y N 5-58
F21
(Braking level) 0% to 80% (LD/MD mode)
*4
, 0% to 100% (HD mode)
Y
Y
0 Y Y Y Y N
F22
(Braking time) 0.00 (Disable); 0.01 to 30.00 s
Y
Y 0.00 Y Y Y Y N
The shaded function codes (
) are applicable to the quick setup.
*1 6.00 s for inverters of 40 HP or below; 20.00 s for those of 50 HP or above
*2 The motor rated current is automatically set. See Table B (P03/A17/b17/r17).
*3 5.0 min for inverters of 40 HP or below; 10.0 min for those of 50 HP or above
*4 0% to 100% for inverters of 7.5 HP or below