5-127
• If the maintenance interval counter reaches the specified value, set a new value for the next maintenance in H78
and press the
key to reset the output signal and restart counting. This function is exclusively applied to the
1st motor.
• If the startup counter reaches the specified value, set a new value for the next maintenance in H79 and press the
key to reset the output signal and restart counting. This function is exclusively applied to the 1st motor.
H45 Mock
Alarm
H97 (Clear Alarm Data)
H45 causes the inverter to generate a mock alarm in order to check whether external sequences function correctly at the time
of machine setup.
Setting the H45 data to "1" displays mock alarm
err
on the LED monitor. It also issues alarm output (for any alarm)
ALM
(if assigned to a digital output terminal by any of E20 to E24 and E27). (Accessing the H45 data requires simultaneous
keying of "
key +
key.") After that, the H45 data automatically reverts to "0," allowing you to reset the alarm.
Just as data (alarm history and relevant information) of those alarms that could occur in running the inverter, the inverter
saves mock alarm data, enabling you to confirm the mock alarm status.
To clear the mock alarm data, use H97. (Accessing the H97 data requires simultaneous keying of "
key +
key.") H97
data automatically returns to "0" after clearing the alarm data.
A mock alarm can be issued also by simultaneous keying of "
key +
key" on the keypad for 5 seconds or more.
H46
Starting Mode (Auto search delay time 2)
(Refer to H09.)
H47, H48
Initial Capacitance of DC Link Bus Capacitor
Cumulative Run Time of Capacitors on Printed Circuit Boards
(Refer to H42.)
H50, H51
H52, H53
Non-linear V/f Pattern 1 (Frequency and Voltage)
Non-linear V/f Pattern 2 (Frequency and Voltage)
(Refer to F04.)
H49
Starting Mode (Auto search delay time 1)
(Refer to H09.)
H54, H55
H56
H57 to H60
Acceleration Time, Deceleration Time (Jogging)
Deceleration Time for Forced Stop
1st/2nd S-curve Acceleration/Deceleration Range
(Refer to F07.)
H61
UP/DOWN Control (Initial frequency setting)
(Refer to F01.)
H63
Low Limiter (Mode selection)
(Refer to F15.)
H64
Low Limiter (Lower limiting frequency)
H64 specifies the lower limit of frequency to be applied when the current limiter, torque limiter, automatic deceleration
(anti-regenerative control), or overload prevention control is activated. Normally, it is not necessary to change this data.
- Data setting range: 0.0 to 60.0 (Hz)
H65, H66
Non-linear V/f Pattern 3 (Frequency and Voltage)
(Refer to F04.)
H67
Auto Energy Saving Operation (Mode selection)
(Refer to F37.)
H68
Slip Compensation 1 (Operating conditions)
(Refer to F42.)