![Fuji Electric FRENIC-MEGA Скачать руководство пользователя страница 339](http://html1.mh-extra.com/html/fuji-electric/frenic-mega/frenic-mega_instruction-manual_2341853339.webp)
8-5
Ch
ap. 8
SPECIFICA
T
IO
NS
8.2 Standard Model 2 (DCR Built-in Type)
8.2.1 Three-phase 230 V series
LD (Low Duty)-mode inverters for light load
Item Specifications
Type
(FRN_
_
_G1H-2U)
007 010
015 020 025
030
040
050
060
075
100
Nominal applied motor
(HP)
*1
(Output rating)
7.5 10
15 20 25 30
40
50
60
75
100
Outp
ut r
a
tin
g
s
Rated capacity (kVA)
*2
11 13
18 24 30 35
46
58
72
86
113
Rated voltage (V)
*3
Three-phase 200 to 240 V (with AVR function)
Three-phase 200 to 230 V
(with AVR function)
Rated current (A)
*4
27
31.8
(29)
46.2
(42)
59.4
(55)
74.8
(68)
88
(80)
115
(107)
146
180
215
283
Overload capability
150%-
1 min,
200%-
3.0 s
120%-1 min
In
pu
t powe
r Voltage, frequency
200 to 240 V, 50/60 Hz
200 to 220 V, 50 Hz,
200 to 230 V, 60 Hz
Allowable
voltage/frequency
Voltage: +10 to -15% (Interphase voltage unbalance: 2% or less)
*5
, Frequency: +5 to -5%
Required capacity
(kVA)
7.7 10
15 20 25 30
40
50
62
74
98
Brak
ing
Torque (%)
*6
70%
15%
7 to 12%
Braking transistor
Built-in
–
Built-in braking resistor
Built-in
–
Braking time (s)
3.7 s
3.4 s
–
Duty cycle (%ED)
2.2
1.4
–
DC reactor (DCR)
Built-in as standard
Applicable safety
standards
UL508C, C22.2 No.14, EN61800-5-1:2007
Enclosure (IEC60529)
IP20, UL open type
IP00, UL open type
Cooling method
Fan cooling
Weight / Mass
lbs (kg)
24
(10.7)
24
(10.7)
25
(11.1)
25
(11.5)
38
(17.3)
39
(17.6)
41
(18.5)
68
(31)
86
(39)
112
(51)
115
(52)
HD (High Duty)-mode inverters for heavy load
Item Specifications
Type (FRN_ _ _G1H-2U) 007
010
015
020
025
030
040
050
060
075
100
Nominal applied motor
(HP)
*1
(Output rating)
7.5 7.5
10 15 20 25
30
40
50
60
75
O
u
tput r
a
ti
ngs
Rated capacity (kVA)
*2
11 11
15 20 25 30
36
47
58
72
86
Rated voltage (V)
*3
Three-phase 200 to 240 V (with AVR function)
Three-phase 200 to 230 V
(with AVR function)
Rated
current
(A)
27 27
37 49 63 76
90
119
146
180
215
Overload capability
150%-1 min, 200%-3.0 s
Inpu
t po
w
e
r Voltage, frequency
200 to 240 V, 50/60 Hz
200 to 220 V, 50 Hz,
200 to 230 V, 60 Hz
Allowable
voltage/frequency
Voltage: +10 to -15% (Interphase voltage unbalance: 2% or less)
*5
, Frequency: +5 to -5%
Required capacity
(kVA)
7.7
7.7
10.5 15.5
21
26
31
42
52
64
77
B
rak
in
g
Torque (%)
*6
100%
20%
10 to 15%
Braking transistor
Built-in
–
Built-in braking resistor
Built-in
–
Braking time (s)
5 s
–
Duty cycle (%ED)
3
2
–
DC reactor (DCR)
Built-in as standard
Applicable safety
standards
UL508C, C22.2 No.14, EN61800-5-1:2007
Enclosure (IEC60529)
IP20, UL open type
IP00, UL open type
Cooling method
Fan cooling
Weight / Mass
lbs (kg)
24
(10.7)
24
(10.7)
25
(11.1)
25
(11.5)
38
(17.3)
39
(17.6)
41
(18.5)
68
(31)
86
(39)
112
(51)
115
(52)
*1 US-4P standard induction motor
*2 Rated capacity is calculated assuming the rated output voltage as 230 V for 230 V series and 460 V for 460 V series.
*3 Output voltage cannot exceed the power supply voltage.
*4 To use the inverter with the carrier frequency of 3 kHz or more at the surrounding temperature of 40°C (104°F) or higher, manage the load so that the
current comes to be within the rated ones enclosed in parentheses ( ) in continuous running.
*5
3)
-
61800
(IEC
67
×
(V)
voltage
average
phase
-
Three
(V)
voltage
Min.
-
(V)
voltage
Max.
(%)
unbalance
Voltage
=
If this value is 2 to 3%, use an optional AC reactor (ACR).
*6 Average braking torque for the motor running alone, without external braking resistor. (It varies with the efficiency of the motor.)
Содержание FRENIC-MEGA
Страница 36: ...2 6 Unit inch mm Refer to Section 2 3 3 9...
Страница 208: ...5 89 Examples of Sequence Circuits 1 Standard sequence 2 Sequence with an emergency switching function...
Страница 356: ...MEMO...
Страница 358: ...Fuji Electric Co Ltd Fuji Electric Corp of America http www fujielectric com fecoa 2011 04 D11 D10...