![Fuji Electric FRENIC-MEGA Скачать руководство пользователя страница 133](http://html1.mh-extra.com/html/fuji-electric/frenic-mega/frenic-mega_instruction-manual_2341853133.webp)
5-14
Ch
ap
. 5
FUNCTION C
O
DES
F codes
E codes
C codes
P codes
H codes
A codes
b codes
r codes
J codes
d codes
U codes
y codes
Code Name
Data
setting
range
Ch
ange wh
e
n
ru
nnin
g
Da
ta
cop
yi
ng
Default
setting
Drive control
Refer
to
page:
V/f
PG
V/f
w/o
PG
w/
PG
Torque
control
H49 Starting Mode
(Auto search delay time 1)
0.0 to 10.0 s
Y Y 0.0
Y
Y
Y
Y
Y
5-119
5-127
H50 Non-linear V/f Pattern 1 (Frequency) 0.0: Cancel, 0.1 to 500.0 Hz
N Y 0.0
Y
Y
N
N
N
5-43
H51
(Voltage) 0 to 240: Output an AVR-controlled voltage
(for 230 V series)
0 to 500: Output an AVR-controlled voltage
(for 460 V series)
N Y2
0 Y
Y
N
N N
5-127
H52 Non-linear V/f Pattern 2 (Frequency) 0.0: Cancel, 0.1 to 500.0 Hz
N Y 0.0
Y
Y
N
N
N
H53
(Voltage) 0 to 240: Output an AVR-controlled voltage
(for 230 V series)
0 to 500: Output an AVR-controlled voltage
(for 460 V series)
N Y2
0 Y
Y
N
N N
H54 Acceleration Time
(Jogging) 0.00 to 6000 s
Y Y *1
Y
Y
Y
Y
N
5-45
H55 Deceleration Time
(Jogging) 0.00 to 6000 s
Y Y *1
Y
Y
Y
Y
N
5-127
H56 Deceleration Time for Forced Stop
0.00 to 6000 s
Y Y *1
Y
Y
Y
Y
N
H57 1st S-curve acceleration range
(Leading
edge)
0% to 100%
Y Y 10
Y
Y
Y
Y
N
H58 2nd S-curve acceleration range
(Trailing
edge)
0% to 100%
Y Y 10
Y
Y
Y
Y
N
H59 1st S-curve deceleration range
(Leading
edge)
0% to 100%
Y Y 10
Y
Y
Y
Y
N
H60 2nd S-curve deceleration range
(Trailing
edge)
0% to 100%
Y Y 10
Y
Y
Y
Y
N
H61 UP/DOWN Control
(Initial frequency setting)
0: 0.00 Hz
1: Last
UP
/
DOWN
command value on releasing the run
command
N Y 1 Y
Y
Y
Y
N
5-34
5-127
H63 Low Limiter
(Mode selection) 0: Limit by F16 (Frequency limiter: Low) and continue to
run
1: If the output frequency lowers below the one limited by
F16 (Frequency limiter: Low), decelerate to stop the
motor.
Y Y 0 Y
Y
Y
Y
N
5-57
5-127
H64
(Lower limiting frequency) 0.0: Depends on F16 (Frequency limiter, Low)
0.1 to 60.0 Hz
Y Y 1.6
Y
Y
N
N
N
5-127
H65 Non-linear V/f Pattern 3 (Frequency) 0.0: Cancel, 0.1 to 500.0 Hz
N Y 0.0
Y
Y
N
N
N
5-43
H66
(Voltage) 0 to 240: Output an AVR-controlled voltage
(for 230 V series)
0 to 500: Output an AVR-controlled voltage
(for 460 V series)
N Y2
0 Y
Y
N
N N
5-127
H67 Auto Energy Saving Operation
(Mode
selection)
0: Enable during running at constant speed
1: Enable in all modes
Y Y 0 Y
Y
N
Y
N
5-64
5-127
H68 Slip Compensation 1
(Operating
conditions)
0: Enable during ACC/DEC and at base frequency or
above
1: Disable during ACC/DEC and enable at base
frequency or above
2: Enable during ACC/DEC and disable at base
frequency or above
3: Disable during ACC/DEC and at base frequency or
above
N Y 0 Y
Y
N
N
N
5-73
5-127
H69 Automatic Deceleration
(Mode
selection)
0: Disable
2: Torque limit control with Force-to-stop if actual
deceleration time exceeds three times the specified
one
3: DC link bus voltage control with Force-to-stop if actual
deceleration time exceeds three times the specified
one
4: Torque limit control with Force-to-stop disabled
5: DC link bus voltage control with Force-to-stop
disabled
Y Y 0 Y
Y
Y
Y
N
5-128
H70 Overload Prevention Control
0.00: Follow the deceleration time selected
0.01 to 100.0 Hz/s
999: Cancel
Y Y 999
Y
Y
Y
Y
N
5-129
H71 Deceleration Characteristics
0: Disable
1: Enable
Y Y 0 Y
Y
N
N
N
H72 Main Power Down Detection
(Mode
selection)
0: Disable
1: Enable
Y Y 1 Y
Y
Y
Y
Y
*1 6.00 s for inverters of 40 HP or below; 20.00 s for those of 50 HP or above