5.2.2 E codes (Extension Terminal Functions)
E01 to E07 Terminal [X1] to [X7] Function
E98 (Terminal [FWD] Function)
E99 (Terminal [REV] Function)
E01 to E07, E98 and E99 assign commands (listed below) to general-purpose, programming, digital input terminals, [X1] to
[X7], [FWD], and [REV].
These function codes can also switch the logic system between normal and negative to define how the inverter logic
interprets the ON or OFF state of each terminal. The factory default setting is normal logic system "Active ON." So,
descriptions that follow are given in normal logic system. They are, in principle, arranged in the numerical order of assigned
data. However, highly relevant signals are collectively described where one of them first appears. Refer to the function
codes in the "Related function codes" column, if any.
The FRENIC-MEGA runs under "V/f control," "dynamic torque vector control," "V/f control with speed sensor," "dynamic
torque vector control with speed sensor," "vector control without speed sensor," or "vector control with speed sensor." Some
terminal commands assigned apply exclusively to the specific drive control, which is indicated by letters Y (Applicable) and
N (Not applicable) in the "Drive control" column in the table given below. (Refer to page 5-2.)
• Ensure safety before modifying the function code settings.
Run commands (e.g., "Run forward"
FWD
), stop commands (e.g., "Coast to a stop"
BX
), and frequency change
commands can be assigned to digital input terminals. Depending upon the assignment states of those terminals,
modifying the function code setting may cause a sudden motor start or an abrupt change in speed.
• When the inverter is controlled with the digital input signals, switching run or frequency command sources with the
related terminal commands (e.g.,
SS1
,
SS2
,
SS4
,
SS8
,
Hz2/Hz1
,
Hz/PID
,
IVS
, and
LE
) may cause a sudden motor
start or an abrupt change in speed.
An accident or physical injury may result.
Function code data
Terminal commands assigned
Symbol
Drive control
Related
function codes
Active ON Active OFF
V/f PG
V/f
w/o
PG
w/
PG
Torque
control
0 1000
Select multi-frequency (0 to 15 steps)
SS1
Y
Y
Y
Y
N
C05 to C19
1 1001
SS2
Y
Y
Y
Y
N
2 1002
SS4
Y
Y
Y
Y
N
3 1003
SS8
Y
Y
Y
Y
N
4
1004
Select ACC/DEC time (2 steps)
RT1
Y
Y
Y
Y
N
F07, F08,
E10 to E15
5
1005
Select ACC/DEC time (4 steps)
RT2
Y
Y
Y
Y
N
6 1006
Enable
3-wire
operation
HLD
Y
Y
Y
Y
Y
F02
7 1007
Coast
to
a
stop
BX
Y
Y
Y
Y
Y
⎯
8 1008
Reset
alarm
RST
Y
Y
Y
Y
Y
⎯
1009
9
Enable external alarm trip
THR
Y
Y
Y
Y
Y
⎯
10 1010
Ready
for
jogging
JOG
Y
Y
Y
Y
N
C20, H54, H55,
d09 to d13
11
1011
Select frequency command 2/1
Hz2/Hz1
Y
Y
Y
Y
N
F01, C30
12
1012
Select motor 2
M2
Y
Y
Y
Y
Y
A42
13
⎯
Enable DC braking
DCBRK
Y
Y
Y
Y
N
F20 to F22
14
1014
Select torque limiter level 2/1
TL2/TL1
Y
Y
Y
Y
Y
F40, F41, E16,
E17
15
⎯
Switch to commercial power (50 Hz)
SW50
Y
Y
N
N
N
⎯
16
⎯
Switch to commercial power (60 Hz)
SW60
Y
Y
N
N
N
⎯
17
1017
UP (Increase output frequency)
UP
Y
Y
Y
Y
N
Frequency
command:
F01, C30
PID command: J02
18
1018
DOWN (Decrease output frequency)
DOWN
Y
Y
Y
Y
N
19
1019
Enable data change with keypad
WE-KP
Y
Y
Y
Y
Y
F00
20
1020
Cancel PID control
Hz/PID
Y
Y
Y
Y
N
J01 to J19,
J56 to J62
21
1021
Switch normal/inverse operation
IVS
Y
Y
Y
Y
N
C53, J01
22 1022
Interlock
IL
Y
Y
Y
Y
Y
F14
23
1023
Cancel torque control
Hz/TRQ
N
N
N
N Y H18
24 1024
Enable communications link via RS-485
or fieldbus (option)
LE
Y
Y
Y
Y
Y
H30, y98
25 1025
Universal
DI
U-DI
Y
Y
Y
Y
Y
⎯